5.12.3 Tag name convention<br />
IO Server Name S73&400<br />
Topic Name<br />
Item Name<br />
General Reference Guide IO Servers Configuration<br />
The Item Name can contain the PLC address where the value is polled, or not. If the address is also specified at the topic level, the address<br />
specified at Tag level will be ignored.<br />
5.12.3.1 Value Name<br />
The syntax is the following:<br />
<br />
A<br />
B<br />
C<br />
ValueName, Global Device Address PLC address is defined Tag by Tag<br />
ValueName Topic PLC Address is used.<br />
Important: All the addresses are always in BYTES (except for Counter and Timer that are objects)<br />
Note: The Modifier can by omitted, the modifier in bold will be used (DB type must have a modifier).<br />
(*) Important: See “Tags are stored as Float” on page 67<br />
Table 100: S73&400 IO server - Tag name convention table<br />
Symbol Memory Type Modifier Address<br />
DBx Data Block number x B, C, W, S, D, L, F Byte offset<br />
M Internal Memory B, C, W, S, D, L, F Byte offset<br />
C Counter W, S Object number<br />
T Timer W, S Object number<br />
I Discrete Inputs B, C, W, S, D, L, F Byte offset<br />
Q Discrete Outputs B, C, W, S, D, L, F Byte offset<br />
PI Peripheral Inputs B, C, W, S, D, L, F Byte offset<br />
PQ Peripheral Outputs B, C, W, S, D, L, F Byte offset<br />
Table 101: S7 300-400 Memory types<br />
Symbol Modifier value range<br />
B Byte 0 .. 255<br />
C signed Byte -128 .. 127<br />
W Word 0 .. 65535<br />
S signed Word -32768 .. 32767<br />
D DWord 0 .. 4294967296 (*)<br />
L signed DWord -2147483648 .. 2147483647 (*)<br />
F Float +/- 3.4e38<br />
Table 102: S7 300-400 Modifiers<br />
RG-001-0-EN ver 1.6 <strong>eWON</strong>® - 22/06/2009 - ©ACT'L sa Page 127