3.4.1.2 Tags validation<br />

General Reference Guide <strong>eWON</strong> Configuration<br />

For optimisation purpose and since firmware version 5.2, the <strong>eWON</strong> can detect if tags are valid or not, and disables the polling of invalid tags.<br />

By default, this feature is not activated, See "Global Config" on page 86 to enable it.<br />

At the creation of the Tags or at the initialisation of an IOServer, all tags are considered as valid and are polled.<br />

If repetitive errors occur on some Tags, these tags will be considered as invalid and will not be polled anymore !<br />

A specific error message will be written in the event log.<br />

This message is "Protocol Error while reading Tag (TagName - Polling disabled for this tag)" (see example in figure below)<br />

Invalid tags will be polled again when:<br />

Figure 60: Tag validation - error event<br />

• the IOServer is started (i.e.: after a IOServer modification)<br />

• a manual INIT of the IOServer (See "IO Server Init" on page 86)<br />

• a modification of the Tag (in the I/O Server Setup part of Tag Setup)<br />

3.4.1.3 Tags monitoring and handling<br />

The <strong>eWON</strong> engine can handle the following operations on the Tags:<br />

Operation Description<br />

Alarm monitoring<br />

Historical logging<br />

Real Time logging<br />

Modbus TCP publishing<br />

3.4.2 Tag definition: Setup<br />

Check for low and high alarm levels or Boolean alarm level and management of alarm<br />

acknowledgement, alarm historical logging and action on alarm (Email, SMS, etc.)<br />

Tags can be monitored and changes on a Tag can be saved in the Flash File System.<br />

Storage can be based on change threshold or at regular interval.<br />

A Tag history can be kept in memory for an amount of time with a given time interval. This<br />

operation is volatile and does not involve any flash storage.<br />

All the Tags can be given a Modbus address and can be read using the Modbus TCP protocol<br />

by and external modbus TCP master.<br />

Tag grouping Tags can be organized by page for easier handling and viewing.<br />

Script Access All the Tags values and attributes can be read or changed from script.<br />

Table 43: Tags operations handled by the <strong>eWON</strong><br />

The Tag Setup page, reachable by clicking on the Tag Setup item of the Configuration menu, offer the possibility to build the <strong>eWON</strong> Tag’s<br />

dictionary.<br />

The Tag name dictionary is the <strong>eWON</strong> central database where you have to define all the Input / Output (internal – available on the <strong>eWON</strong> – or<br />

external – through extension bus) that you want the <strong>eWON</strong> to monitor. If your Input/Output is not defined by a Tag, you will not be able to address<br />

it.<br />

The Tag configuration includes two parts:<br />

• The complete Tag configuration except for the actions to execute in case of an alarm.<br />

• The alarm action list.<br />

The first part of the configuration is accessed through the Tag hyperlink; the second part is accessed with the icon next to the Tag hyperlink.<br />

Note: In the header menu of the Tag edition, a combo box appears with a list of pages (please refer to chapter “Pages configuration”<br />

on page 79). Only the Tags of the selected page will be displayed in the list, except if "ALL" is selected.<br />

RG-001-0-EN ver 1.6 <strong>eWON</strong>® - 22/06/2009 - ©ACT'L sa Page 68