5.10.2.3.2 PT100 input AI5 and AI6<br />

These two entries measure a Resistance value in Ohm.<br />

General Reference Guide IO Servers Configuration<br />

AI# Ohm<br />

0 162.13<br />

4095 79.625<br />

As you can see, the slope is negative, and if you need to read the Tag value converted in Ohm, you can set a factor of -0.02014774 = -82.505/<br />

4095 with an offset of 162.13.<br />

Figure 94: Tag’s configuration: reading the tag value in Ohms<br />

If you need to convert into °C: temperature = AI * (-0.0523311) + 161.376.<br />

The default range of PT100 in <strong>eWON</strong> is -50°C to 150°C.<br />

Full range of ADC is: -52.92°C to 161.376°C (79.625 Ohm to 162.13 Ohm).<br />

Note:<br />

• <strong>eWON</strong> 4002 models prior to S/N 0517-xxxx-89 have a PT100 range from 0°C to 131.9°C and must apply the following formulas:<br />

Ohm = IOValue * (-0.012402) + 150.8<br />

°C = IOValue * (-0.0322) + 131.9<br />

• <strong>eWON</strong> 4002 models from S/N 0517-xxxxx-89 to S/N 0521-xxxx-89 have a PT100 range from -56°C to 151°C and must apply the<br />

following formulas:<br />

Ohm = IOValue * (-0.0195068) + 158.2<br />

°C = IOValue * (-0.050677) + 151.2<br />

RG-001-0-EN ver 1.6 <strong>eWON</strong>® - 22/06/2009 - ©ACT'L sa Page 122