NAVAL DOCKYARD, MUMBAI<br />

TITLE : QUALITY ASSURANCE PLAN DOC CODE Q C L 7 4 Q A P 0 6 3<br />

DEPT. :<br />

QC(ELECTRICAL )<br />

C. NO. 74 ISSUE NO : 00 DATE : 15 Apr 12 PAGE 02 OF 14<br />

5. QC CHECKS TO BE UNDERTAKEN AS PER SOW/ CHECK LIST :<br />

Sr. ACTIVITY<br />

No. DESCRIPTION<br />

REFERENCE DOCMENT & CHECK LIST INSPECTION<br />

SCOPE OF WORK P R W H<br />

01 Repair, Overhaul<strong>in</strong>g, Refer to QAP : QCL074QAP001 for Alternator 1 2&3 3 3<br />

refurbishment, new (i) Checks dur<strong>in</strong>g removal and open<strong>in</strong>g <strong>in</strong>spection,<br />

<strong>in</strong>stallation and Check for tech<strong>nic</strong>al details of removed / opened<br />

commission<strong>in</strong>g/Test<strong>in</strong>g Alternator for any damage /miss<strong>in</strong>g /<br />

of Alternator / abnormalities . Check for serviceability / condition<br />

Generator<br />

of Alternator for to ascerta<strong>in</strong> the serviceability of<br />

each components to undertake repair/ overhaul /<br />

renewal.<br />

ii) Check for old & New bear<strong>in</strong>gs to be QC checked<br />

before fitment at QC bear<strong>in</strong>g Lab.<br />

iii) Check w<strong>in</strong>d<strong>in</strong>g ohmic values & <strong>in</strong>sulation of w<strong>in</strong>d<strong>in</strong>g.<br />

iv) Check for overhaul<strong>in</strong>g and clean<strong>in</strong>g of all by CTC /<br />

alcohol / petrol Alternator parts like body, w<strong>in</strong>d<strong>in</strong>g, rotor,<br />

shaft, rocker<br />

Arms, carbon brusher & AVR . Defective parts to be<br />

renewed as per sample and reputed / OEM make<br />

conform<strong>in</strong>g IS.<br />

v) Carbon brusher to be renewed as per grade & size<br />

confirm<strong>in</strong>g IS<br />

vi) If w<strong>in</strong>d<strong>in</strong>g found burnt/over heated/Zero <strong>in</strong>sulation<br />

(Not improved even overhaul<strong>in</strong>g) to be rewound as per<br />

orig<strong>in</strong>al data.<br />

vii) New procured w<strong>in</strong>d<strong>in</strong>g wire to be QC checked <strong>in</strong> the<br />

QC WWT Lab<br />

viii) Dr bake varnish / coat varnish to be applied on the<br />

w<strong>in</strong>d<strong>in</strong>g.<br />

viii) Rotor to be balanced and trueness checked.<br />

Certificate to be provided .<br />

ix) Shaft bear<strong>in</strong>g size to be checked, if found changes<br />

then rotor shaft built up/mach<strong>in</strong>ed by fabrication &<br />

mach<strong>in</strong><strong>in</strong>g.<br />

x) Check rotor bar open / crack / shorted with shaft to be<br />

repaired, if It found beyond then to be renewed as per<br />

design.<br />

xi) Check for <strong>in</strong>spection for <strong>in</strong>sulation & proper<br />

assembl<strong>in</strong>g, fitment, alignment and connections.<br />

xiii) Check for term<strong>in</strong>al block, term<strong>in</strong>al connections<br />

cables lugs, cable glands. Check for <strong>in</strong>sulation of Cable<br />

1 2&3 3 3<br />

DYT/INCOD/12­13/106(a)/PL­YCM/MADHUR­REFIT/420 67/127