i) Check for meters serviceability, If found unserviceable<br />
then meters<br />
to be replaced as per OEM make/ sample/AE make<br />
NAVAL DOCKYARD, MUMBAI<br />
TITLE : QUALITY ASSURANCE PLAN DOC CODE Q C L 7 4 Q A P 0 6 3<br />
DEPT. :<br />
QC(ELECTRICAL )<br />
C. NO. 74 ISSUE NO : 00 DATE : 15 Apr 12 PAGE 04 OF 14<br />
Sr. ACTIVITY<br />
No. DESCRIPTION<br />
REFERENCE DOCMENT & CHECK LIST INSPECTION<br />
SCOPE OF WORK P R W H<br />
j) Check for <strong>in</strong>ternal wir<strong>in</strong>g for jo<strong>in</strong>ts, parish, & unsecure.<br />
To be renewed as per sample/ rat<strong>in</strong>g. Check for fitment,<br />
tightness, secur<strong>in</strong>g of <strong>in</strong>ternal wir<strong>in</strong>g. m) Check for<br />
pa<strong>in</strong>t, identification tallies.<br />
n) Check for operational performance of <strong>in</strong>dications,<br />
switch gears then test<strong>in</strong>g of full switch board.<br />
o) New material spare to be offered for QC checks<br />
prior to fitment bill voucher to be submitted<br />
03 Repair, Overhaul<strong>in</strong>g,<br />
refurbishment, new<br />
<strong>in</strong>stallation and<br />
commission<strong>in</strong>g/Test<strong>in</strong>g<br />
of AC/DC Motor<br />
Refer to QAP : QCL074QAP001 for AC/DC Motor<br />
(i) Checks dur<strong>in</strong>g removal and open<strong>in</strong>g <strong>in</strong>spection,<br />
Check for tech<strong>nic</strong>al details of removed / opened<br />
Alternator for any damage /miss<strong>in</strong>g /<br />
abnormalities . Check for serviceability / condition<br />
of Alternator for to ascerta<strong>in</strong> the serviceability of<br />
each components to undertake repair/ overhaul /<br />
renewal. ii) Check for old & New bear<strong>in</strong>gs to be QC<br />
1 2&3 3 3<br />
checked before fitment at QC bear<strong>in</strong>g Lab. iii)<br />
Check w<strong>in</strong>d<strong>in</strong>g ohmic values & <strong>in</strong>sulation of<br />
w<strong>in</strong>d<strong>in</strong>g. iv) Check for overhaul<strong>in</strong>g and clean<strong>in</strong>g of<br />
all by CTC / alcohol / petrol Alternator parts like<br />
body, w<strong>in</strong>d<strong>in</strong>g, rotor, shaft, rocker Arms, carbon<br />
brusher & Defective parts to be renewed as per<br />
sample and reputed / OEM make conform<strong>in</strong>g IS. v<br />
) Carbon brusher to be renewed as per grade &<br />
size confirm<strong>in</strong>g IS vi) If w<strong>in</strong>d<strong>in</strong>g found burnt/over<br />
heated/Zero <strong>in</strong>sulation (Not improved even<br />
overhaul<strong>in</strong>g) to be rewound as per orig<strong>in</strong>al data. vii<br />
) New procured w<strong>in</strong>d<strong>in</strong>g wire to be QC checked <strong>in</strong><br />