12<br />

Starting from the (already fixed) vertical section to the very left, align<br />

and fix the remaining vertical sections one after the other. Proceed as<br />

follows: push the corresponding vertical section towards the duct roof<br />

until it comes to a stop. Then, align the section parallel to the preceding<br />

section on the left by means of a bracket for the upper flow sheets.<br />

Finally, fix the screws of the respective clamping brackets.<br />

Important! At the interstice with system-specific width the bracket for<br />

the upper flow sheet marked with a “V” must be used as spacer.<br />

Important! The brackets for the upper flow sheets serve as spacers<br />

only and must not be mounted yet.<br />

50mm<br />

50mm<br />

V<br />

ø3.3 mm<br />

12. Mount the angle brackets to the upper end of all vertical sections and<br />

fix them with the M6x12 hexagon socket screws provided (slightly<br />

tighten by hand only).<br />

Align the vertical section to the very left at right angle to the cross arm.<br />

Then, push the angle bracket towards the duct roof and fix it to the duct<br />

roof using two self-tapping screws provided (drill holes ø3.3 mm<br />

before).<br />

Starting from the vertical section to the very left, align all other vertical<br />

sections one after the other and fix them with the angle brackets to the<br />

duct roof. Proceed as follows: align the corresponding section parallel<br />

to the preceding section on the left by means of a bracket for the upper<br />

flow sheets. Then, push the angle bracket to the duct roof and fix it using<br />

two self-tapping screws provided (drill holes ø3.3 mm before). Finally<br />

fasten the M6x12 hexagon socket screw in the vertical section.<br />

Important! At the interstice with system-specific width the bracket for<br />

the upper flow sheet marked with a “V” must be used as a spacer.<br />

Important! The brackets for the upper flow sheets serve as spacers<br />

only and must not be mounted yet (their final installation is explained<br />

in the following section).<br />

V<br />

50mm<br />

50mm<br />

25