6.4 Replacement of silver ionization “Hygieneplus”<br />
Ag electrode<br />
change due<br />
Ag electrode<br />
change due<br />
error 12<br />
Ag ion<br />
On commissioning, the current of the silver ionization must be adjusted by<br />
the technician in accordance with the table in chapter 9.4. Following the<br />
results of a germ test the settings may be changed at any time later on.<br />
If the silver ionization cartridge needs to be replaced (capacity counter<br />
reads 0) the display alternately shows the standard operation mode display<br />
and the opposite message. In case the control unit is equipped with the<br />
optional remote operation and fault indication PCB, the latter additionally<br />
issues an error. In this case it is mandatory to replace the silver<br />
ionization cartridge with a new one.<br />
If you do not reset the message “Ag electrode change due” (see below), the<br />
unit is automatically powered off after about one week of operation and the<br />
display alternately shows the two opposite messages (also refer to chapter<br />
7.1 “Error messages”).<br />
Resetting the capacity counter<br />
Following the replacement of the silver ionization cartridge the capacity<br />
counter needs to be reset as follows:<br />
Press and hold both arrow keys key while switching the control unit<br />
on. Keep both arrow keys depressed (approx. 5 seconds) until the red<br />
error LED goes off and then comes on again briefly (approx. 1 second).<br />
Replacing the silver ionization cartridge<br />
• Set the hybrid humidifier <strong>Condair</strong> <strong>Dual</strong> out of operation as per chapter<br />
5.3 and depressurize the water system.<br />
• Remove the two electrical connectors from the connections on the silver<br />
ionization cartridge.<br />
• Loosen the hose connectors at the entry and the exit, then remove both<br />
screw-in nipples.<br />
Caution! The silver ionization cartridge is filled with fully demineralized<br />
water. Place a bucket under the cartridge before loosening the connections.<br />
• Undo the four screws fastening the silver ionization cartridge to the<br />
holder, then remove the cartridge.<br />
Caution! The empty silver ionization cartridge weighs approx. 3 kg<br />
(6.5 lb).<br />
• Install the new silver ionization cartridge in the reverse order.<br />
Caution! Exhausted silver ionization cartridges must be sent to the local<br />
<strong>Condair</strong> representative for correct disposal.<br />