6.5 Replacement of the control unit fuses<br />

64<br />

F3 (6.3 AT)<br />

The fuses of the control unit must be replaced by authorized personnel<br />

only (e.g. electrician).<br />

Caution! Electronic components are sensitive to electrostatic discharge.<br />

Protective measures (ESD protection) must be taken before replacing the<br />

fuse(s) of the control unit.<br />

Replace fuses F1 and F3 of the control unit only with fuses matching the<br />

specifications below:<br />

– Fuse F1: fuse type: 2 A, slow-blow<br />

– Fuse F3: fuse type: 6.3 A, slow-blow<br />

Caution! Never use refurbished fuses. Do not bridge the fuse holder.<br />

F1 (2 AT)<br />