9 Appendix<br />

9.1 Notes on humidity control<br />

9.1.1 Notes on humidity control with the internal PI controller<br />

The internal PI controller of the <strong>Condair</strong> <strong>Dual</strong> Hybrid Humidifier<br />

The controller built into the <strong>Condair</strong> <strong>Dual</strong> Hybrid Humidifier is a so-called PI<br />

controller (proportional-integral controller). The PI controller interprets the<br />

analog signal as the actual humidity value captured by a sensor and<br />

controls the humidification capacity via the “proportional range” and “integral<br />

time” parameters.<br />

– Proportional range (P-range)<br />

The proportional range is used to smoothen the control characteristic.<br />

The larger the selected P-range, the smoother the control characteristic<br />

will be. However, this results in a permanent control deviation (from the<br />

preset nominal value), proportional to the bandwidth of the P-range.<br />

Note: Minor deviations may be compensated by optimal coordination<br />

with the integral time parameter.<br />

– Integral time<br />

The integral time setting determines the period allowed to balance the<br />

deviation of the control (due to the P-range) and to reach the nominal<br />

value. The greater the integral time setting, the longer it takes to reach<br />

the nominal humidity (providing better accuracy).<br />

The smaller the integral time value, the faster the nominal humidity will<br />

be reached (reduced control accuracy).<br />

Controller settings<br />

No general advice can be given on how to adjust the built-in PI controller<br />

of the <strong>Condair</strong> <strong>Dual</strong> Hybrid Humidifier (P-range and integral time settings)<br />

because every control distance (distance between humidifier and measuring<br />

spot) presents a particular degree of difficulty in terms of adjustment.<br />

However, the following rules may be used as a guideline when adjusting the<br />

PI controller:<br />

• Always start from the factory settings.<br />

• In case control requires fine-tuning:<br />

• Change values in small steps only.<br />

• Always modify the P-range first.<br />

• Never alter the P-Range and integral time settings simultaneously.<br />

71