56<br />
P-band<br />
10 %<br />
integr.time<br />
15 Min<br />
– Proportional range (P-range) of the internal PI controller<br />
Sets the proportional range of the internal PI controller in %.<br />
Note: This parameter is available only if the internal PI controller is<br />
active.<br />
Factory setting: 10 %<br />
Setting range: 4 - 100 %<br />
Note: The proportional range is used to smoothen the control characteristic.<br />
The larger the selected P-range, the smoother the control<br />
characteristic will be. However, this results in a permanent control<br />
deviation, proportional to the bandwidth of the P-range. For further<br />
information please refer to chapter 9.1.<br />
– Integral time of the internal PI controller<br />
Determines the integral time of the internal PI controller in minutes.<br />
Note: This parameter is available only if the internal PI controller is<br />
active.<br />
Factory setting: 15 minutes<br />
Optional settings: off (no integral time), 2 - 100 minutes<br />
Note: The integral time setting determines the period allowed to<br />
reach the nominal humidity. Setting the integral time to the optimal<br />
value prevents the control characteristic from overshooting and, at<br />
the same time, balances the permanent deviation (caused by the<br />
proportional range setting). For further information please refer to<br />
chapter 9.1.