5.3 Taking the humidifier out of operation<br />
To take the <strong>Condair</strong> <strong>Dual</strong> Hybrid Humidifier out of operation, e.g. for maintenance<br />
purposes, proceed as follows:<br />
• Set the power switch to “O”.<br />
• Disconnect the control unit from the mains: Set the service switch<br />
of the mains supply line to “Off”.<br />
• Close the shut-off valve of the water supply conduit.<br />
Note: If the water supply system requires maintenance depressurize<br />
the water system first. For this purpose switch the control unit back on<br />
again and wait until flushing is concluded and the alarm message<br />
no. 07 “minimum permeate pressure” appears on the display. Then,<br />
switch the control unit off again, as described above.<br />
• Mind hygiene! Let the fan of the ventilation system run until the<br />
humidification unit is dry.<br />
• In case the humidification unit requires maintenance switch the ventilation<br />
system off and secure it against unintentional power-up.<br />
Important information on extended periods of non-use<br />
Important! For reasons of hygiene, we basically recommend that the<br />
Hybrid Humidifier should be left switched on, even in periods when there<br />
is no requirement for humidification. With the system switched on, the water<br />
circuit is flushed at regular intervals and hence the build-up of germs is<br />
opposed.<br />
However, if it is necessary to leave the Hybrid Humidifier switched off for<br />
long periods, the following points should be noted:<br />
– Mind hygiene! Drain all water conduits.<br />
– For safety reasons the post-evaporation elements should remain in<br />
their working position, even if the humidifier is not used for an extended<br />
period. This prevents the water from being sprayed directly into the<br />
duct in case the humidifier is powered up inadvertently.<br />
47