7.2 Failures<br />

Residual water in the section of<br />

the duct outside the water tub<br />

<strong>Condair</strong> <strong>Dual</strong> humidifies permanently<br />

Spray valves open and close<br />

continually<br />

Maximum humidification capacity<br />

is not reached<br />

Booster pump starts too late or<br />

not at all<br />

Pressure at the manometer of<br />

the connector box drops to 0<br />

bar during operation<br />

Spray valve Y6 (stage 1) and/or<br />

spray valve Y7 (stage 2) do not<br />

open<br />

68<br />

The following table presents failures that do not trigger an error message,<br />

together with indications on their cause and notes on how to eliminate the<br />

sources of trouble.<br />

Failure Cause Remedy<br />

Sealing elements improperly<br />

installed or defective.<br />

Post-evaporation elements<br />

improperly installed or ceramic<br />

plates broken.<br />

Air velocity in the duct is too high<br />

(systems without booster<br />

>2.5 m/s, systems with booster<br />

>4 m/s).<br />

Nominal value of humidity is too<br />

high.<br />

Ambient humidity very low.<br />

The internal sensor of the control<br />

unit is active although an external<br />

sensor is connected.<br />

Set nominal value correctly.<br />

Wait.<br />

Deactivate the internal sensor of<br />

the control unit (see chapter 5.5).<br />

Unstable controller signal. Check controller settings and<br />

adjust controller, as required.<br />

Output limitation active.<br />

System incorrectly dimensioned<br />

(insufficient capacity).<br />

Booster pump defective (insufficient<br />

permeate pressure).<br />

Output limitation active and/or<br />

selected starting point of booster<br />

pump is too high.<br />

Fuse F3 blown.<br />

Water hose(s) between spray valves<br />

and spray nozzles (or hoses inside<br />

the duct) disconnected.<br />

Working pressure is too low.<br />

Spray valve Y6 and/or spray valve<br />

Y7 defective.<br />

Output limitation active.<br />

Mount sealing elements correctly<br />

or replace, as required.<br />

Mount ceramic plates correctly or<br />

replace, as required.<br />

Reduce air velocity in the duct, if<br />

possible, or install booster (consult<br />

your <strong>Condair</strong> supplier beforehand).<br />

Deactivate output limitation (see<br />

chapter 5.5).<br />

Contact your <strong>Condair</strong> supplier.<br />

Replace booster pump.<br />

Deactivate output limitation (setting:<br />

100%, see chapter 5.5) and/<br />

or adjust starting point of booster<br />

pump (call service technician).<br />

Replace fuse.<br />

Attach water hose(s).<br />

Check reverse osmosis system<br />

and fully demineralized water<br />

supply conduit.<br />

Replace spray valves.<br />

Deactivate output limitation (setting:<br />

100%, see chapter 5.5).