7.2 Failures<br />
Residual water in the section of<br />
the duct outside the water tub<br />
<strong>Condair</strong> <strong>Dual</strong> humidifies permanently<br />
Spray valves open and close<br />
continually<br />
Maximum humidification capacity<br />
is not reached<br />
Booster pump starts too late or<br />
not at all<br />
Pressure at the manometer of<br />
the connector box drops to 0<br />
bar during operation<br />
Spray valve Y6 (stage 1) and/or<br />
spray valve Y7 (stage 2) do not<br />
open<br />
68<br />
The following table presents failures that do not trigger an error message,<br />
together with indications on their cause and notes on how to eliminate the<br />
sources of trouble.<br />
Failure Cause Remedy<br />
Sealing elements improperly<br />
installed or defective.<br />
Post-evaporation elements<br />
improperly installed or ceramic<br />
plates broken.<br />
Air velocity in the duct is too high<br />
(systems without booster<br />
>2.5 m/s, systems with booster<br />
>4 m/s).<br />
Nominal value of humidity is too<br />
high.<br />
Ambient humidity very low.<br />
The internal sensor of the control<br />
unit is active although an external<br />
sensor is connected.<br />
Set nominal value correctly.<br />
Wait.<br />
Deactivate the internal sensor of<br />
the control unit (see chapter 5.5).<br />
Unstable controller signal. Check controller settings and<br />
adjust controller, as required.<br />
Output limitation active.<br />
System incorrectly dimensioned<br />
(insufficient capacity).<br />
Booster pump defective (insufficient<br />
permeate pressure).<br />
Output limitation active and/or<br />
selected starting point of booster<br />
pump is too high.<br />
Fuse F3 blown.<br />
Water hose(s) between spray valves<br />
and spray nozzles (or hoses inside<br />
the duct) disconnected.<br />
Working pressure is too low.<br />
Spray valve Y6 and/or spray valve<br />
Y7 defective.<br />
Output limitation active.<br />
Mount sealing elements correctly<br />
or replace, as required.<br />
Mount ceramic plates correctly or<br />
replace, as required.<br />
Reduce air velocity in the duct, if<br />
possible, or install booster (consult<br />
your <strong>Condair</strong> supplier beforehand).<br />
Deactivate output limitation (see<br />
chapter 5.5).<br />
Contact your <strong>Condair</strong> supplier.<br />
Replace booster pump.<br />
Deactivate output limitation (setting:<br />
100%, see chapter 5.5) and/<br />
or adjust starting point of booster<br />
pump (call service technician).<br />
Replace fuse.<br />
Attach water hose(s).<br />
Check reverse osmosis system<br />
and fully demineralized water<br />
supply conduit.<br />
Replace spray valves.<br />
Deactivate output limitation (setting:<br />
100%, see chapter 5.5).