5 Operation<br />
5.1 Introduction<br />
8<br />
I/O<br />
5.2 Commissioning for daily operation<br />
test<br />
The <strong>Condair</strong> <strong>Dual</strong> Hybrid Humidifier must be commissioned and operated<br />
only by personnel familiar with the unit and adequately qualified<br />
for the task. Ascertaining the qualification is the customer’s responsibility.<br />
The <strong>Condair</strong> <strong>Dual</strong> Hybrid Humidifier is operated via the control unit. The<br />
control unit provides the following display and control elements:<br />
1<br />
XXXXXXXXXXXXXXXX<br />
XXXXXXXXXXXXXXXX<br />
M E<br />
6<br />
2 3 4 5 7<br />
1 Display<br />
(5x7 dot matrix, 2x16 characters)<br />
2 key (menu key)<br />
3 key (arrow key up)<br />
4 key (arrow key down)<br />
5 key (entry key)<br />
6 “Error” indicator (red LED)<br />
7 “Humidification on” indicator<br />
(green LED)<br />
8 key (power switch)<br />
The following description outlines the commissioning procedure for daily<br />
operation. It is assumed that first-time commissioning has been carried out<br />
properly by the service technician of your <strong>Condair</strong> supplier. Proceed as<br />
follows to prepare the <strong>Condair</strong> <strong>Dual</strong> Hybrid Humidifier for operation:<br />
• Check the installation and all system components for damage.<br />
Caution! Do not put the system into operation in case of damaged<br />
installations or system components.<br />
• Make sure the ceramic plates are correctly located and properly sealed.<br />
Caution! Put the system into operation only if the above requirements<br />
are met without fail.<br />
• Set the mains supply service switch (power supply to control unit) to<br />
“On”.<br />
• First set the power switch of the control unit to “I”, then open the shutoff<br />
valve of the water supply conduit. The control system now carries<br />
out a basic system test while the “Humidification on” and “Error”<br />
indicators light up. Once the test is completed the drain valve opens for<br />
approximately 20 seconds (flushing of the permeate conduit).<br />
45