50<br />
perform. [kg/h]<br />
appliance: 100<br />
perform. [kg/h]<br />
act.value: 33<br />
unity anal.entry<br />
25 %<br />
unity anal.entry<br />
25 %<br />
p-pump. int/ext<br />
intern<br />
cond. permeate<br />
7 ‰S<br />
permeate limit<br />
15 ‰S<br />
perform. [kg/h]<br />
valve Y6: 35<br />
perform. [kg/h]<br />
valve Y7: 55<br />
perform. [kg/h]<br />
valve Y8: 75<br />
contr.val.p-pump<br />
95 %<br />
Description of display level parameters<br />
The following description explains the parameters that may be accessed<br />
via the and keys once the display level has been launched (with<br />
the or key).<br />
– Maximum humidification output<br />
Maximum spraying capacity in kg/hr.<br />
– Current humidification output<br />
Current spraying capacity in kg/hr.<br />
Note: The actual spraying capacity may differ from the displayed value<br />
depending on the current spraying pressure.<br />
– Analog input (humidification request)<br />
Current signal value at the analog input in % of the maximum value.<br />
Note: If the internal controller is active the displayed value corresponds<br />
to the current ambient humidity in %rh.<br />
– Booster pump internal/external<br />
This display indicates whether the control unit is configured to work with<br />
an internal or external booster pump.<br />
– Conductance<br />
Current conductance of the permeate in µS.<br />
– Permeate limit<br />
Selected limit value of permeate conductance in µS.<br />
Note: If this value is exceeded in operation, the drain valve (Y5) of the<br />
connector box is opened until the conductance of the permeate drops<br />
below the given limit value again.<br />
– Spraying capacity of spray valve 1<br />
Nominal spraying capacity of open spray valve 1 (Y6) in kg/hr (at a<br />
spraying pressure of approximately 7 bar).<br />
– Spraying capacity of spray valve 2<br />
Nominal spraying capacity of open spray valve 2 (Y7) in kg/hr (at a<br />
spraying pressure of approximately 7 bar).<br />
– Spraying capacity of spray valve 3 (option)<br />
Nominal spraying capacity of open spray valve 3 (Y8) in kg/hr (at a<br />
spraying pressure of approximately 7 bar).<br />
Note: A nominal spraying capacity value of 0 is displayed if the optional<br />
spray valve 3 is not available.<br />
– Starting point of booster pump<br />
Starting point of the booster pump in % of the maximum humidification<br />
request.<br />
Note: This parameter is available only if the control unit is configured to<br />
work with an internal booster pump.