6.3.2 Removal and installation of the spray nozzles<br />

62<br />

Removal of the spray nozzles<br />

• Remove the hose(s) from the spray nozzle (press the locking ring<br />

towards screw, then pull hose off).<br />

• Squeeze the catch locks of the nozzle support and remove the support.<br />

Note: The nozzles may have different spraying capacities (max. 2 different<br />

capacities per system). Nozzles with identical capacity are marked<br />

with bushings of the same color (A). We recommend you note the<br />

positions and capacities of all nozzles before removal.<br />

• Use an open-end wrench (16 mm) to loosen and remove the nipple and<br />

the nozzle.<br />

Installation of the spray nozzles<br />

Before installation check all parts for possible damage. Damaged components<br />

must not be reinstalled.<br />

Replace all sealings of the nozzle with new ones.<br />

Important! Flush all conduits with fully demineralized water before assembling<br />

the unit.<br />

For installation proceed in the reverse order of removal.<br />

– Make sure to install the nozzles in their correct positions in the nozzle<br />

lattice (see installation drawing).<br />

– Following installation verify correct fastening of all hose connectors.<br />

Correctly mounted hoses can not be removed without pressing the<br />

locking ring.