7 What if ...?<br />

7.1 Error messages<br />

alarm 04<br />

limit permeate<br />

alarm 07<br />

min.press. perm.<br />

alarm 08<br />

max.press. perm.<br />

alarm 09<br />

permeate temp.<br />

Faults detected during operation trigger the fault indicator (red LED) and<br />

a corresponding event message appears on the display. The <strong>Condair</strong> <strong>Dual</strong><br />

makes a distinction between alarms and errors.<br />

Alarms<br />

An alarm indicates a temporary fault that was detected during operation<br />

(short-time interruption of the water supply) or faults that do not cause<br />

damage to the system. If the source of trouble disappears within 30<br />

minutes, the alarm is reset automatically. Otherwise, the system issues<br />

a corresponding error message.<br />

Indication: red LED flashes (once a second)<br />

alarm message appears on the display<br />

Example:<br />

Alarm message Cause/Remedy<br />

alarm 10<br />

Ag ion current<br />

alarm 09<br />

permeate temp.<br />

Cause: Permeate conductance (limit) required for stopping permeate flushing<br />

is not reached even after extended flushing.<br />

Remedy: Check reverse osmosis system.<br />

Cause: Pressure at fully demineralized water connector of booster pump is too<br />

low (cause: water conduit too narrow, reverse osmosis system too<br />

small or too many consuming devices connected to reverse osmosis<br />

system).<br />

Remedy: Check reverse osmosis system and fully demineralized water supply<br />

conduit. Pressure at fully demineralized water connector must be at<br />

least 2 bar (working pressure). Install larger supply conduits (min.<br />

inner ø 15 mm).<br />

This message appears only if the system is equipped with built-in booster pump!<br />

Cause: Admissible maximum pressure of permeate exceeded.<br />

Remedy: Check reverse osmosis system and/or setting of booster pump. Integrate<br />

a pressure regulator into the supply line.<br />

Cause: Operating temperature of booster pump is too high or flat ribbon cable<br />

between power supply PCB and CPU PCB (inside the control unit) is<br />

disconnected or defective.<br />

Remedy: Check booster pump. Plug in flat ribbon cable or replace cable, as<br />

required.<br />

Reduce temperature of fully demineralized water supply (max. 45 °C).<br />

Cause: Nominal value of ionization current not reached (cable defective or<br />

disconnected, silver electrodes worn).<br />

Remedy: Check/Re-establish electrical connection of silver ionization. Replace<br />

silver ionization cartridge (see chapter 6.4).<br />

65