Fault message Cause/Remedy<br />

error 05<br />

conduct. perm.<br />

error 06<br />

cond.meas. perm.<br />

error 10<br />

Ag ion current<br />

error 11<br />

Ag ion test<br />

error 12<br />

Ag ion<br />

error 13<br />

sensor<br />

Cause: Conductance limit exceeded (>100 µS/cm).<br />

Remedy: Check reverse osmosis system (max. conductance 15 µS/cm), check<br />

conductance sensor and clean, if required.<br />

Cause: Permeate conductance out of admissible range of tolerance (conductance<br />

sensor disconnected or short-circuited).<br />

Remedy: Check reverse osmosis system. Connect conductance sensor on connector<br />

box, check wiring.<br />

Cause: Nominal or maximum value of silver ionization current is not reached<br />

(error message 10 present for more than a week).<br />

Remedy: Check/plug in connection cables of silver ionization unit. Replace silver<br />

ionization cartridge. Measure ionic current at 100% humidifying capacity<br />

and compare to setup value.<br />

Cause: At the daily Ag ion test the maximum ionization current could not be<br />

reached because the silver electrodes are partially or fully worn (error<br />

message 11 present for more than a week).<br />

Remedy: Replace silver ionization cartridge (see chapter 6.4).<br />

Cause: The silver ionization cartridge was not replaced although the message<br />

“Ag electrode change due” has been present for more than a week, or<br />

the capacity counter was not reset following the replacement of the<br />

cartridge.<br />

Remedy: Replace silver ionization cartridge and/or reset the capacity counter<br />

(see chapter 6.4).<br />

Cause: If the internal controller is activated and the humidity signal of the<br />

connected humidity sensor is below 5% for more than 10 minutes the<br />

connection to the sensor is interrupted or the humidity sensor is<br />

defective.<br />

The internal controller is activated although an external controller is<br />

connected.<br />

Remedy: Check connection cable, humidity sensor and control signal setting or<br />

replace humidity sensor.<br />

Disable the internal controller if an external controller is connected.<br />