Fault message Cause/Remedy<br />
error 05<br />
conduct. perm.<br />
error 06<br />
cond.meas. perm.<br />
error 10<br />
Ag ion current<br />
error 11<br />
Ag ion test<br />
error 12<br />
Ag ion<br />
error 13<br />
sensor<br />
Cause: Conductance limit exceeded (>100 µS/cm).<br />
Remedy: Check reverse osmosis system (max. conductance 15 µS/cm), check<br />
conductance sensor and clean, if required.<br />
Cause: Permeate conductance out of admissible range of tolerance (conductance<br />
sensor disconnected or short-circuited).<br />
Remedy: Check reverse osmosis system. Connect conductance sensor on connector<br />
box, check wiring.<br />
Cause: Nominal or maximum value of silver ionization current is not reached<br />
(error message 10 present for more than a week).<br />
Remedy: Check/plug in connection cables of silver ionization unit. Replace silver<br />
ionization cartridge. Measure ionic current at 100% humidifying capacity<br />
and compare to setup value.<br />
Cause: At the daily Ag ion test the maximum ionization current could not be<br />
reached because the silver electrodes are partially or fully worn (error<br />
message 11 present for more than a week).<br />
Remedy: Replace silver ionization cartridge (see chapter 6.4).<br />
Cause: The silver ionization cartridge was not replaced although the message<br />
“Ag electrode change due” has been present for more than a week, or<br />
the capacity counter was not reset following the replacement of the<br />
cartridge.<br />
Remedy: Replace silver ionization cartridge and/or reset the capacity counter<br />
(see chapter 6.4).<br />
Cause: If the internal controller is activated and the humidity signal of the<br />
connected humidity sensor is below 5% for more than 10 minutes the<br />
connection to the sensor is interrupted or the humidity sensor is<br />
defective.<br />
The internal controller is activated although an external controller is<br />
connected.<br />
Remedy: Check connection cable, humidity sensor and control signal setting or<br />
replace humidity sensor.<br />
Disable the internal controller if an external controller is connected.<br />
67