5.5 Setting up operating parameters<br />

52<br />

intgr.time<br />

15 Min.<br />

perform. limit<br />

100 %<br />

analog signal<br />

0-10 Vdc ( 81%)<br />

error history<br />

07/ 10/ 08/ 07<br />

software version<br />

V6.00<br />

<strong>Condair</strong> <strong>Dual</strong><br />

ready<br />

entry<br />

setup level<br />

entry code<br />

9999<br />

entry code<br />

8999<br />

– Integral time of internal controller<br />

Preset integral time of the internal controller in minutes.<br />

Note: This parameter is available only if the internal controller is<br />

active.<br />

– Output limitation<br />

Preset limit value of output in % of the maximum output capacity.<br />

– Analog signal<br />

Range of the selected analog signal in V or mA, respectively.<br />

Note: The value in brackets is the current value in % of the maximum<br />

signal or the current ambient humidity in %rh, respectively.<br />

– Error history<br />

Numeric codes of the 4 most recent errors (example: “07”: last error,<br />

“10”: second to last error, etc.).<br />

Note: Information on the meaning of error codes is given in chapter 7.<br />

– Software version<br />

Current version of the control unit software.<br />

In the setup level you may adjust various operating parameters to adapt<br />

the <strong>Condair</strong> <strong>Dual</strong> Hybrid Humidifier to your particular requirements.<br />

Important! The adjustments made in the setup level immediately exercise<br />

an influence on the operating characteristics of the hybrid humidifier. Therefore,<br />

adjustments must be made only by persons having sufficient knowledge<br />

in the field of humidification and air-conditioning technology and being<br />

familiar with the <strong>Condair</strong> <strong>Dual</strong> Hybrid Humidifier.<br />

Accessing the setup level<br />

The <strong>Condair</strong> <strong>Dual</strong> is in standard operation mode (the display of the control<br />

unit shows the current operating status).<br />

• Simultaneously press the and keys to access the setup level.<br />

The opposite message is displayed briefly.<br />

You are now prompted to enter the 4-digit access code. The leftmost digit<br />

flashes.<br />

• Enter the access code “8808” as follows:<br />

Change the first digit using the and keys. Confirm your entry<br />

with the key. The next digit starts flashing.<br />

Repeat this step to change the remaining digits.