4.3 Installation of the central unit<br />
Location of the central unit<br />
– The central unit is designed for wall mounting. Make sure the construction<br />
(wall, pillar, etc.) to which the central unit is to be mounted, offers<br />
a sufficiently high load-bearing capacity and is suitable for the installation.<br />
Caution! Do not mount the central unit to vibrating parts.<br />
– The central unit must be installed only in a location having a water<br />
drain on the floor. If this is not possible, it is mandatory to provide water<br />
sensors to safely interrupt water supply in case of leakage. Furthermore,<br />
choose a suitable location that prevents damage to material<br />
assets in case of leakage.<br />
– Make sure the ambient conditions at the desired location meet the<br />
specifications outlined in chapter 8.2.<br />
– Danger of damage! Do not install the central unit in exposed locations<br />
or locations with heavy dust load. Use the optional casing (option<br />
“Z408”) to protect the central unit from damage and soiling, or use the<br />
central unit with spray circle discharge integrated in two protective cabinets<br />
(option “Z409”).<br />
– Install the central unit so that the water hoses between the connector<br />
box and the nozzles are as short as possible (max. 10 m).<br />
– Install the central unit in a freely accessible location providing enough<br />
space for operation and maintenance (0,5 m minimum clearance<br />
around the central unit, distance to floor at least 1 m).<br />
Installation of the central unit<br />
Use the provided fastening set to mount the central unit to the wall or to the<br />
monobloc. If for some special reasons an installation with the supplied<br />
fastening material is not feasible, choose a type of installation that is equally<br />
stable.<br />
Important! Use a level for accurate horizontal adjustment.<br />
900 mm<br />
640 mm<br />
ø10 mm<br />
ø8x50 mm<br />
Z408<br />
35