3.7 I/O Card Interface Variables %I and %Q<br />

This type of variable is associated with the following elements:<br />

- 32-discrete-input cards,<br />

- 32-discrete-output cards,<br />

- 32-discrete-input/24-discrete-output card,<br />

- 32-24 I/O cards,<br />

- 64-48 I/O card,<br />

- machine panel,<br />

- machine panel 32-discrete-input/24-discrete-output extension cards.<br />

Each interface discrete I/O card includes:<br />

- a block of 64 bytes of %I read variables<br />

- a block of 64 bytes of %Q write variables.<br />

Variables<br />

The I/O cards are addressed logically (see Sec. 3.7.4) on four digits. The default value (no reconfiguration) is:<br />

I<br />

%<br />

Q<br />

Logical @ = geographic @<br />

Rack No.<br />

(0 to 6)<br />

Card No.<br />

(1 to C)<br />

r c<br />

Logical @<br />

(0 to 3F)<br />

The card number c and rack number r are related to the type of equipment. Refer to the Installation and Commissioning<br />

Manual for rack addressing.<br />

Equipment type Rack number Card number<br />

Main 19" rack 0 5 to C<br />

Main 12" rack 0 5 to 8<br />

12-card extension rack 1 to 6 1 to C<br />

2-card extension rack 1 to 6 1 and 2<br />

Machine panel 0 1 to 4<br />

Example<br />

%I3500 Represents read byte 0 on card 5 in rack 3.<br />

%Q652F Represents write byte 0x2F on card 5 in rack 6.<br />

REMARK Logical (as opposed to geographical) addressing is also possible (see Sec. 3.7.4).<br />

en-938846/6 3 - 9<br />

3