3.7.12 Image Part of the Extension Operator Panel Card<br />

Card Identifier %Irc3E.W == 0x200.<br />

Format of register %Irc3C.W<br />

Variable type Input or output type Variables<br />

Variables<br />

Power supply failure 1 = 24V present<br />

Power supply failure 0 = 24V absent<br />

Output 0 group short-circuit 1 = No short-circuit<br />

Output 1 group short-circuit 0 = Short-circuit<br />

Group 0 input link failure<br />

Group 1 input link failure 1 = Failure<br />

Group 0 output link failure<br />

Group 1 output link failure<br />

0 = OK<br />

%Irc00 Discrete inputs 0 to 7 %Irc00.0 (Input 0) to %Irc00.7 (Input 7)<br />

%Irc01 Discrete inputs 8 to 15 %Irc01.0 (Input 8) to %Irc01.7 (Input 15)<br />

%Irc02 Discrete inputs 16 to 23 %Irc02.0 (Input 16) to %Irc02.7 (Input 23)<br />

%Irc03 Discrete inputs 24 to 31 %Irc03.0 (Input 24) to %Irc03.7 (Input 31)<br />

%Irc04 Discrete inputs 32 to 39 %Irc04.0 (Input 32) to %Irc04.7 (Input 39)<br />

%Irc10 Discrete inputs 40 to 47 %Irc10.0 (Input 40) to %Irc10.7 (Input 47)<br />

%Irc11 Discrete inputs 48 to 55 %Irc11.0 (Input 48) to %Irc11.7 (Input 55)<br />

%Irc12 Discrete inputs 56 to 63 %Irc12.0 (Input 56) to %Irc12.7 (Input 63)<br />

%Irc13 Discrete inputs 64 to 71 %Irc13.0 (Input 64) to %Irc13.7 (Input 71)<br />

%Irc20.W Analogue input 0<br />

%Irc22.W Analogue input 1<br />

%Qrc00 Discrete outputs 0 to 7 %Qrc00.0 (Output 0) to %Qrc00.7 (Output 7)<br />

%Qrc01 Discrete outputs 8 to 15 %Qrc01.0 (Output 8) to %Qrc01.7 (Output 15)<br />

%Qrc02 Discrete outputs 16 to 23 %Qrc02.0 (Output 16) to %Qrc02.7 (Output 23)<br />

%Qrc10 Discrete outputs 24 to 31 %Qrc10.0 (Output 24) to %Qrc10.7 (Output 31)<br />

%Qrc11 Discrete outputs 32 to 39 %Qrc11.0 (Output 32) to %Qrc11.7 (Output 39)<br />

%Qrc12 Discrete outputs 40 to 47 %Qrc12.0 (Output 40) to %Qrc12.7 (Output 47)<br />

REMARK The panel output LED test must not be conducted in a single operation. In the PLC<br />

programme, first test half the LEDs then test the other half.<br />