D - MV & LV architecture selection guide<br />

Characteristic to<br />

consider<br />

Configuration<br />

LV MV<br />

For the different possible configurations, the most probable and usual set <strong>of</strong><br />

characteristics is given in the following table:<br />

Simple-line Ring-main Duplicate supply Duplicate supply<br />

with double<br />

busbars<br />

Activity Any Any Any Hi-tech, sensitive<br />

<strong>of</strong>fice, health-care<br />

Site topology Single building Single building Single building Single building Several buildings<br />

Service reliability Minimal Minimal Standard Enhanced Enhanced<br />

Power demand < 630kVA ≤ 1250kVA ≤ 2500kVA > 2500kVA > 2500kVA<br />

Other connection<br />

constraints<br />

Any Isolated site Low density urban<br />

area<br />

a) Single feeder: b) Open ring, 1 MV substation:<br />

MV MV MV MV MV<br />

LV<br />

MLVS 1<br />

LV<br />

MLVS n<br />

Fig. D9 : MV circuit configuration<br />

LV<br />

MLVS 1<br />

6 Choice <strong>of</strong> architecture<br />

fundamentals<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

High density<br />

urban area<br />

6.2 MV circuit configuration<br />

Any<br />

Urban area with<br />

utility constraint<br />

The main possible connection configurations are as follows (Fig. D9):<br />

b single feeder, one or several transformers<br />

b open ring, one MV incomer<br />

b open ring, 2 MV incomers<br />

The basic configuration is a radial single-feeder architecture, with one single<br />

transformer.<br />

In the case <strong>of</strong> using several transformers, no ring is realised unless all <strong>of</strong> the<br />

transformers are located in a same substation.<br />

Closed-ring configuration is not taken into account.<br />

LV<br />

MLVS 2<br />

LV<br />

MLVS n<br />

c) Open ring, 2 MV substations:<br />

MV<br />

LV<br />

MLVS 1<br />

MV<br />

LV<br />

MLVS 2<br />

MV<br />

LV<br />

MLVS n