14.11.2012 Views

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

B 0<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

Supply <strong>of</strong> power at medium<br />

voltage<br />

The strategy in this case, is to reduce the resistance <strong>of</strong> the substation earth<br />

electrode, such that the standard value <strong>of</strong> 5-second withstand-voltage-to-earth for<br />

LV equipment and appliances will not be exceeded.<br />

Practical values adopted by one national <strong>electrical</strong> power-supply authority, on its<br />

20 kV distribution systems, are as follows:<br />

b Maximum earth-fault current in the neutral connection on overhead line distribution<br />

systems, or mixed (O/H line and U/G cable) systems, is 300 A<br />

b Maximum earth-fault current in the neutral connection on underground systems is<br />

1,000 A<br />

The formula required to determine the maximum value <strong>of</strong> earthing resistance Rs at<br />

the<br />

the<br />

substation,<br />

substation,<br />

to<br />

to<br />

ensure<br />

ensure<br />

that<br />

that<br />

the<br />

the<br />

LV<br />

LV<br />

withstand<br />

withstand<br />

voltage<br />

voltage will<br />

will<br />

not<br />

not<br />

be<br />

be<br />

exceeded,<br />

exceeded,<br />

is:<br />

is:<br />

Uw �Uo<br />

Rs = in ohms (see cases C and D in Figure B10). C10).<br />

Im<br />

Where<br />

Where<br />

Uw = the lowest standard value (in volts) <strong>of</strong> short-term (5 s) withstand voltage for the<br />

consumer’s <strong>installation</strong> and appliances = Uo + 1200 V (IEC 60364-4-44)<br />

Uo = phase to neutral voltage (in volts) at the consumer’s LV service position<br />

Im = maximum earth-fault current on the MV system (in amps). This maximum earth<br />

fault current Im is the vectorial sum <strong>of</strong> maximum earth-fault current in the neutral<br />

connection and total unbalanced capacitive current <strong>of</strong> the network.<br />

A third form <strong>of</strong> system earthing referred to as the “IT” system in IEC 60364 is<br />

commonly used where continuity <strong>of</strong> supply is essential, e.g. in hospitals, continuousprocess<br />

manufacturing, etc. The principle depends on taking a supply from an<br />

unearthed source, usually a transformer, the secondary winding <strong>of</strong> which is<br />

unearthed, or earthed through a medium impedance (u1,000 ohms). In these cases,<br />

an insulation failure to earth in the low-voltage circuits supplied from the secondary<br />

windings will result in zero or negligible fault-current flow, which can be allowed to<br />

persist until it is convenient to shut-down the affected circuit to carry out repair work.<br />

Diagrams B, D and F (Figure B10)<br />

They show IT systems in which resistors (<strong>of</strong> approximately 1,000 ohms) are included<br />

in the neutral earthing lead.<br />

If however, these resistors were removed, so that the system is unearthed, the<br />

following notes apply.<br />

Diagram B (Figure B10)<br />

All phase wires and the neutral conductor are “floating” with respect to earth, to which<br />

they are “connected” via the (normally very medium) insulation resistances and (very<br />

small) capacitances between the live conductors and earthed metal (conduits, etc.).<br />

Assuming perfect insulation, all LV phase and neutral conductors will be raised by<br />

electrostatic induction to a potential approaching that <strong>of</strong> the equipotential conductors.<br />

In practice, it is more likely, because <strong>of</strong> the numerous earth-leakage paths <strong>of</strong> all live<br />

conductors in a number <strong>of</strong> <strong>installation</strong>s acting in parallel, that the system will behave<br />

similarly to the case where a neutral earthing resistor is present, i.e. all conductors<br />

will be raised to the potential <strong>of</strong> the substation earth.<br />

In these cases, the overvoltage stresses on the LV insulation are small or nonexistent.<br />

Diagrams D and F (Figure B10)<br />

In these cases, the medium potential <strong>of</strong> the substation (S/S) earthing system acts on<br />

the isolated LV phase and neutral conductors:<br />

b Through the capacitance between the LV windings <strong>of</strong> the transformer and the<br />

transformer tank<br />

b Through capacitance between the equipotential conductors in the S/S and the<br />

cores <strong>of</strong> LV distribution cables leaving the S/S<br />

b Through current leakage paths in the insulation, in each case.<br />

At positions outside the area <strong>of</strong> influence <strong>of</strong> the S/S earthing, system capacitances<br />

exist between the conductors and earth at zero potential (capacitances between<br />

cores are irrelevant - all cores being raised to the same potential).<br />

The result is essentially a capacitive voltage divider, where each “capacitor” is<br />

shunted by (leakage path) resistances.<br />

In general, LV cable and <strong>installation</strong> wiring capacitances to earth are much<br />

larger, and the insulation resistances to earth are much smaller than those <strong>of</strong> the<br />

corresponding parameters at the S/S, so that most <strong>of</strong> the voltage stresses appear at<br />

the substation between the transformer tank and the LV winding.<br />

The rise in potential at consumers’ <strong>installation</strong>s is not likely therefore to be a problem<br />

where the MV earth-fault current level is restricted as previously mentioned.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!