F - Protection against electric shock<br />

10,000<br />

1,000<br />

500<br />

300<br />

250<br />

200<br />

150<br />

130<br />

100<br />

60<br />

40<br />

10<br />

t (ms)<br />

15<br />

30<br />

Fig. F34 : Total discrimination at 2 levels<br />

Fig. F35 : Total discrimination at 2 levels<br />

A<br />

A<br />

60<br />

100<br />

RCD 300 mA<br />

type S<br />

Relay with separate<br />

toroidal CT 3 A<br />

delay time 500 ms<br />

RCD<br />

30 mA<br />

Fig. F36 : Total discrimination at 3 or 4 levels<br />

B<br />

RCCB 1 A<br />

delay time 250 ms<br />

C<br />

150<br />

B<br />

RCCB 300 A<br />

delay time 50 ms<br />

or type S<br />

D<br />

RCCB<br />

30 mA<br />

300<br />

500<br />

600<br />

1,000<br />

5 Implementation <strong>of</strong> the TT system<br />

Discrimination at 2 levels (see Fig. F35)<br />

Protection<br />

b Level A: RCD time-delayed setting I (for industrial device) or type S (for domestic<br />

device) for protection against indirect contacts<br />

b Level B: RCD instantaneous, with high sensitivity on circuits supplying socketoutlets<br />

or appliances at high risk (washing machines, etc.) See also <strong>Chapter</strong> P<br />

Clause 3<br />

Schneider Electric solutions<br />

b Level A: Compact or Multi 9 circuit-breaker with adaptable RCD module<br />

(Vigi NS160 or Vigi NC100), setting I or S type<br />

b Level B: Circuit-breaker with integrated RCD module (DPN Vigi) or adaptable<br />

RCD module (e.g. Vigi C60 or Vigi NC100) or Vigicompact<br />

Note: The setting <strong>of</strong> upstream RCCB must comply with selectivity <strong>rules</strong> and take into<br />

account all the downstream earth leakage currents.<br />

Discrimination at 3 or 4 levels (see Fig. F36)<br />

Protection<br />

b Level A: RCD time-delayed (setting III)<br />

b Level B: RCD time-delayed (setting II)<br />

b Level C: RCD time-delayed (setting I) or type S<br />

b Level D: RCD instantaneous<br />

Schneider Electric solutions<br />

b Level A: Circuit-breaker associated with RCD and separate toroidal transformer<br />

(Vigirex RH54A)<br />

b Level B: Vigicompact or Vigirex<br />

b Level C: Vigirex, Vigicompact or Vigi NC100 or Vigi C60<br />

b Level D:<br />

v Vigicompact or<br />

v Vigirex or<br />

v Multi 9 with integrated or adaptable RCD module : Vigi C60 or DPN Vigi<br />

Note: The setting <strong>of</strong> upstream RCCB must comply with selectivity <strong>rules</strong> and take into<br />

account all the downstream earth leakage currents<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Current<br />

(mA)<br />

1 1.5 10 100 500 1,000 (A)<br />

II<br />

I<br />

selective RCDs<br />

domestic S<br />

and industrial<br />

(settings I and II)<br />

RCD 30 mA<br />

general domestic<br />

and industrial setting 0<br />

F21<br />