F - Protection against electric shock<br />

A<br />

RCD<br />

Fig. F29 : Distribution circuits<br />

RCD<br />

B<br />

RCD<br />

RA1 RA2<br />

Distant location<br />

5 Implementation <strong>of</strong> the TT system<br />

5.1 Protective measures<br />

Protection against indirect contact<br />

<strong>General</strong> case<br />

Protection against indirect contact is assured by RCDs, the sensitivity IΔn <strong>of</strong> which<br />

50 V<br />

complies with the condition I �n i (1) (1)<br />

RA<br />

The choice <strong>of</strong> sensitivity <strong>of</strong> the residual current device is a function <strong>of</strong> the resistance<br />

RA <strong>of</strong> the earth electrode for the <strong>installation</strong>, and is given in Figure F28.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

IΔn Maximum resistance <strong>of</strong> the earth electrode<br />

(50 V) (25 V)<br />

3 A 16 Ω 8 Ω<br />

1 A 50 Ω 25 Ω<br />

500 mA 100 Ω 50 Ω<br />

300 mA 166 Ω 83 Ω<br />

30 mA 1666 Ω 833 Ω<br />

Fig. F28 : The upper limit <strong>of</strong> resistance for an <strong>installation</strong> earthing electrode which must not be<br />

exceeded, for given sensitivity levels <strong>of</strong> RCDs at U L voltage limits <strong>of</strong> 50 V and 25 V<br />

Case <strong>of</strong> distribution circuits (see Fig. F29)<br />

IEC 60364-4-41 and a number <strong>of</strong> national standards recognize a maximum tripping<br />

time <strong>of</strong> 1 second in <strong>installation</strong> distribution circuits (as opposed to final circuits). This<br />

allows a degree <strong>of</strong> selective discrimination to be achieved:<br />

b At level A: RCD time-delayed, e.g. “S” type<br />

b At level B: RCD instantaneous<br />

Case where the exposed conductive parts <strong>of</strong> an appliance, or group <strong>of</strong><br />

appliances, are connected to a separate earth electrode (see Fig. F30)<br />

Protection against indirect contact by a RCD at the circuit-breaker level protecting<br />

each group or separately-earthed individual appliance.<br />

In each case, the sensitivity must be compatible with the resistance <strong>of</strong> the earth<br />

electrode concerned.<br />

High-sensitivity RCDs (see Fig. F31)<br />

Fig. F30 : Separate earth electrode Fig. F31 : Circuit supplying socket-outlets<br />

(1) 25 V for work-site <strong>installation</strong>s, agricultural establishments, etc.<br />

According to IEC 60364-4-41, high sensitivity RCDs (y 30 mA) must be used for<br />

protection <strong>of</strong> socket outlets with rated current y 20 A in all locations. The use <strong>of</strong> such<br />

RCDs is also recommended in the following cases:<br />

b Socket-outlet circuits in wet locations at all current ratings<br />

b Socket-outlet circuits in temporary <strong>installation</strong>s<br />

b Circuits supplying laundry rooms and swimming pools<br />

b Supply circuits to work-sites, caravans, pleasure boats, and travelling fairs<br />

See 2.2 and chapter P, section 3<br />

F19<br />