G - Sizing and protection <strong>of</strong> conductors<br />

2 Practical method for determining<br />

the smallest allowable crosssectional<br />

area <strong>of</strong> circuit conductors<br />

2.4 Busbar trunking systems<br />

The selection <strong>of</strong> busbar trunking systems is very straightforward, using the data<br />

provided by the manufacturer. Methods <strong>of</strong> <strong>installation</strong>, insulation materials, correction<br />

factors for grouping are not relevant parameters for this technology.<br />

The cross section area <strong>of</strong> any given model has been determined by the manufacturer<br />

based on:<br />

b The rated current,<br />

b An ambient air temperature equal to 35 °C,<br />

b 3 loaded conductors.<br />

Rated current<br />

The rated current can be calculated taking account <strong>of</strong>:<br />

b The layout,<br />

b The current absorbed by the different loads connected along the trunking system.<br />

Ambient temperature<br />

A correction factor has to be applied for temperature higher than 35 °C. The<br />

correction factor applicable to medium and high power range (up to 4,000 A) is given<br />

in Figure G23a.<br />

°C 35 40 45 50 55<br />

Correction factor 1 0.97 0.93 0.90 0.86<br />

Fig. G23a : Correction factor for air temperature higher than 35 °C<br />

Neutral current<br />

Where 3 rd harmonic currents are circulating, the neutral conductor may be carrying a<br />

significant current and the corresponding additional power losses must be taken into<br />

account.<br />

Figure G23b represents the maximum admissible phase and neutral currents (per<br />

unit) in a high power busbar trunking system as functions <strong>of</strong> 3 rd harmonic level.<br />

Maximum admissible current (p.u)<br />

1.4<br />

1.2<br />

1<br />

0.8<br />

0.6<br />

0.4<br />

0.2<br />

0<br />

0 10 20 30 40<br />

Fig. G23b : Maximum admissible currents (p.u.) in a busbar trunking system as functions <strong>of</strong> the<br />

3 rd harmonic level.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

50 60 70<br />

3 rd harmonic current level (%)<br />

Neutral conductor<br />

Phase conductor<br />

80 90