14.11.2012 Views

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

B34<br />

© Schneider Electric - all rights reserved<br />

B - Connection to the MV public<br />

distribution network<br />

MV distribution<br />

panels for<br />

which standby<br />

supply is<br />

required<br />

Automatic<br />

changeover<br />

panel<br />

Busbar<br />

transition<br />

panel<br />

From standby generator<br />

P y 20,000 kVA<br />

To remainder<br />

<strong>of</strong> the MV<br />

switchboard<br />

Fig. B33 : Section <strong>of</strong> MV switchboard including standby supply<br />

panel<br />

5 The consumer substation<br />

with MV metering<br />

5.2 Choice <strong>of</strong> panels<br />

A substation with MV metering includes, in addition to the panels described in 4.2,<br />

panels specifically <strong>design</strong>ed for metering and, if required, for automatic or manual<br />

changeover from one source to another.<br />

Metering and general protection<br />

These two functions are achieved by the association <strong>of</strong> two panels:<br />

b One panel containing the VT<br />

b The main MV circuit-breaker panel containing the CTs for measurement and<br />

protection<br />

The general protection is usually against overcurrent (overload and short-circuit) and<br />

earth faults. Both schemes use protective relays which are sealed by the powersupply<br />

utility.<br />

Substation including generators<br />

Generator in stand alone operation<br />

If the <strong>installation</strong> needs great power supply availability, a MV standby generator set<br />

can be used. In such a case, the <strong>installation</strong> must include an automatic changeover.<br />

In order to avoid any posssibility <strong>of</strong> parallel operation <strong>of</strong> the generator with the power<br />

supply network, a specific panel with automatic changeover is needed (see Fig. B33).<br />

b Protection<br />

Specific protective devices are intended to protect the generator itself. It must be<br />

noted that, due to the very low short-circuit power <strong>of</strong> the generator comparing with<br />

the power supply network, a great attention must be paid to protection discrimination.<br />

b Control<br />

A voltage regulator controlling an alternator is generally arranged to respond to a<br />

reduction <strong>of</strong> voltage at its terminals by automatically increasing the excitation current<br />

<strong>of</strong> the alternator, until the voltage is restored to normal. When it is intended that<br />

the alternator should operate in parallel with others, the AVR (Automatic Voltage<br />

Regulator) is switched to “parallel operation” in which the AVR control circuit is<br />

slightly modified (compounded) to ensure satisfactory sharing <strong>of</strong> kvars with the other<br />

parallel machines.<br />

When a number <strong>of</strong> alternators are operating in parallel under AVR control, an<br />

increase in the excitation current <strong>of</strong> one <strong>of</strong> them (for example, carried out manually<br />

after switching its AVR to Manual control) will have practically no effect on the voltage<br />

level. In fact, the alternator in question will simply operate at a lower power factor<br />

(more kVA, and therefore more current) than before.<br />

The power factor <strong>of</strong> all the other machines will automatically improve, such that the<br />

load power factor requirements are satisfied, as before.<br />

Generator operating in parallel with the utility supply network<br />

To connect a generator set on the network, the agreement <strong>of</strong> the power supply utility<br />

is usually required. <strong>General</strong>ly the equipement (panels, protection relays) must be<br />

approved by the utility.<br />

The following notes indicate some basic consideration to be taken into account for<br />

protection and control.<br />

b Protection<br />

To study the connection <strong>of</strong> generator set, the power supply utility needs some data<br />

as follows :<br />

v Power injected on the network<br />

v Connection mode<br />

v Short-circuit current <strong>of</strong> the generator set<br />

v Voltage unbalance <strong>of</strong> the generator<br />

v etc.<br />

Depending on the connection mode, dedicated uncoupling protection functions are<br />

required :<br />

v Under-voltage and over-voltage protection<br />

v Under-frequency and over-frequency protection<br />

v Zero sequence overvoltage protection<br />

v Maximum time <strong>of</strong> coupling (for momentary coupling)<br />

v Reverse real power<br />

For safety reasons, the switchgear used for uncoupling must also be provided<br />

with the characteristics <strong>of</strong> a disconnector (i.e total isolation <strong>of</strong> all active conductors<br />

between the generator set and the power supply network).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!