14.11.2012 Views

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

N - Characteristics <strong>of</strong> particular sources and loads<br />

Lamp<br />

power (W)<br />

4 Lighting circuits<br />

Number <strong>of</strong> lamps per circuit<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20<br />

MCB rating C tripping curve<br />

50 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10<br />

80 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16<br />

125 6 6 6 10 10 10 10 10 10 10 10 16 16 16 16 16 16 16 20 20<br />

250 6 10 10 16 16 16 16 16 16 20 20 25 25 25 32 32 32 32 40 40<br />

400 6 16 20 25 25 32 32 32 32 32 32 40 40 40 50 50 50 50 63 63<br />

1000 16 32 40 50 50 50 50 63 63 - - - - - - - - - - -<br />

MCB rating D tripping curve<br />

50 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10<br />

80 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16<br />

125 6 6 6 6 6 6 10 10 10 10 10 16 16 16 16 16 16 16 20 20<br />

250 6 6 10 10 10 10 16 16 16 20 20 25 25 25 32 32 32 32 40 40<br />

400 6 10 16 16 20 20 25 25 25 32 32 40 40 40 50 50 50 50 63 63<br />

1000 10 20 25 32 40 40 50 63 63 - - - - - - - - - - -<br />

Fig. N54 : High pressure mercury vapour (with ferromagnetic ballast and PF correction) - Vac = 230 V<br />

Lamp<br />

power (W)<br />

Number <strong>of</strong> lamps per circuit<br />

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20<br />

MCB rating C tripping curve<br />

Ferromagnetic ballast<br />

18 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

26 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

35/36 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

55 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10<br />

91 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16 16<br />

131 6 6 6 10 10 10 10 10 10 10 10 10 16 16 16 16 16 16 16 20<br />

135 6 6 6 10 10 10 10 10 10 10 10 16 16 16 16 16 16 20 20 20<br />

180 6 6 10 10 10 10 10 10 16 16 16 16 20 20 20 20 25 25 25 25<br />

Electronic ballast<br />

36 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

55 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

66 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10<br />

91 6 6 6 6 6 10 10 10 10 10 10 10 10 10 10 10 16 16 16 16<br />

MCB rating D tripping curve<br />

Ferromagnetic ballast<br />

18 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

26 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

35/36 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

55 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10<br />

91 6 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 16 16 16 16<br />

131 6 6 6 6 6 6 6 10 10 10 10 10 16 16 16 16 16 16 16 20<br />

135 6 6 6 6 6 6 10 10 10 10 10 16 16 16 16 16 16 20 20 20<br />

180 6 6 6 6 10 10 10 10 16 16 16 16 20 20 20 20 25 25 25 25<br />

Electronic ballast<br />

36 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

55 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6<br />

66 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 10 10 10<br />

91 6 6 6 6 6 6 6 6 6 10 10 10 10 10 10 10 16 16 16 16<br />

Fig. N55 : Low pressure sodium (with PF correction) - Vac = 230 V<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

N39<br />

© Schneider Electric - all rights reserved