H - LV switchgear: functions & selection<br />

Discrimination based on time-delayed tripping<br />

uses CBs referred to as “selective” (in some<br />

countries).<br />

Implementation <strong>of</strong> these CBs is relatively simple<br />

and consists in delaying the instant <strong>of</strong> tripping<br />

<strong>of</strong> the several series-connected circuit-breakers<br />

in a stepped time sequence<br />

(1) Short-delay<br />

4 Circuit-breaker<br />

Fault<br />

upstream<br />

<strong>of</strong> B<br />

Fault<br />

downstream<br />

<strong>of</strong> B<br />

b The upstream circuit-breaker is a high speed device with a short-delay (SD) feature<br />

These circuit-breakers are fitted with trip units which include a non-adjustable<br />

mechanical short-time-delay feature. The delay is sufficient to ensure total<br />

discrimination with any downstream high-speed CB at any value <strong>of</strong> short-circuit<br />

current up to Ii A (see Fig. H54).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

I peak<br />

Fig. H53 : Downstream limiting circuit-breaker B<br />

t<br />

A<br />

Is c<br />

Fig. H54 : Use <strong>of</strong> a “selective” circuit-breaker upstream<br />

B<br />

A<br />

Current limitation<br />

curves<br />

(see note)<br />

B<br />

Only B opens A and B open<br />

Im A<br />

delayed<br />

Is c<br />

prospective (rms)<br />

Ii A<br />

instantaneous<br />

Example<br />

Circuit-breaker A: Compact NS250 N fitted with a trip unit which includes a SD<br />

feature.<br />

Ir = 250 A, magnetic trip set at 2,000 A<br />

Circuit-breaker B: Compact NS100N<br />

Ir = 100 A<br />

The Merlin Gerin distribution catalogue indicates a discrimination limit <strong>of</strong> 3,000 A (an<br />

improvement over the limit <strong>of</strong> 2,500 A obtained when using a standard tripping unit).<br />

Time-based discrimination<br />

This technique requires:<br />

b The introduction <strong>of</strong> time-delays into the tripping mechanisms <strong>of</strong> CBs<br />

b CBs with adequate thermal and mechanical withstand capabilities at the high<br />

current levels and time delays considered<br />

Two circuit-breakers A and B in series (i.e. carrying the same current) are<br />

discriminative if the current-breaking period <strong>of</strong> downstream circuit-breaker B is less<br />

than the non-tripping time <strong>of</strong> circuit-breaker A.<br />

I<br />

H25<br />

© Schneider Electric - all rights reserved