N48<br />

© Schneider Electric - all rights reserved<br />

N - Characteristics <strong>of</strong> particular sources and loads<br />

Among the many possible methods <strong>of</strong><br />

protecting a motor, the association <strong>of</strong> a<br />

circuit breaker + contactor + thermal relay (1)<br />

provides many advantages<br />

(1) The combination <strong>of</strong> a contactor with a thermal relay is<br />

commonly referred to as a “discontactor”<br />

5 Asynchronous motors<br />

The types <strong>of</strong> co-ordination<br />

For each association <strong>of</strong> devices, a type <strong>of</strong> co-ordination is given, according to the<br />

state <strong>of</strong> the constituant parts following a circuit-breaker trip out on fault, or the<br />

opening <strong>of</strong> a contactor on overload.<br />

The standard IEC 947-4-1 defines two types <strong>of</strong> co-ordination, type 1 and type 2,<br />

which set maximum allowable limits <strong>of</strong> deterioration <strong>of</strong> switchgear, in case <strong>of</strong> shortcircuit.<br />

Whatever the type <strong>of</strong> co-ordination, it is required that the contactor or the starter must<br />

never present a danger for the personnel and for the <strong>installation</strong>. The specificities <strong>of</strong><br />

each type are:<br />

b Type 1<br />

Deterioration <strong>of</strong> the starter is acceptable after a short-circuit and the operation <strong>of</strong> the<br />

starter may be recovered after reparing or replacing some parts.<br />

b Type 2<br />

Burning and the risk <strong>of</strong> welding <strong>of</strong> the contacts <strong>of</strong> the contactor are the only risks<br />

allowed.<br />

Which type to choose?<br />

The type <strong>of</strong> co-ordination to adopt depends on the parameters <strong>of</strong> exploitation and must<br />

be chosen to satisfy (optimally) the needs <strong>of</strong> the user and the cost <strong>of</strong> <strong>installation</strong>.<br />

b Type 1<br />

v Qualified maintenance service<br />

v Volume and cost <strong>of</strong> switchgear reduced<br />

v May not be suitable for further service without repair or replacement <strong>of</strong> parts after<br />

a short-circuit<br />

b Type 2<br />

v Only light maintenance measures for further use after a short-circuit<br />

5.3 Applications<br />

The control and protection <strong>of</strong> a motor can consist <strong>of</strong> one, two, three or four different<br />

devices which provide one or several functions.<br />

In the case <strong>of</strong> the combination <strong>of</strong> several devices, co-ordination between them<br />

is essential in order to provide optimized protection <strong>of</strong> the motor application.<br />

To protect a motor circuit, many parameters must be taken into account. They<br />

depend on:<br />

b The application (type <strong>of</strong> driven machine, safety <strong>of</strong> operation, number <strong>of</strong> operations,<br />

etc.)<br />

b The continuity performance requested by the application<br />

b The standards to be enforced to provide security and safety.<br />

The <strong>electrical</strong> functions to be provided are quite different:<br />

b Start, normal operation and stop without unexpected tripping while maintaining<br />

control requirements, number <strong>of</strong> operations, durability and safety requirements<br />

(emergency stops), as well as circuit and motor protection, disconnection (isolation)<br />

for safety <strong>of</strong> personnel during maintenance work.<br />

Basic protection schemes: circuit-breaker + contactor<br />

+ thermal relay<br />

Avantages<br />

The combination <strong>of</strong> devices facilitates <strong>installation</strong> work, as well as operation and<br />

maintenance, by:<br />

b The reduction <strong>of</strong> the maintenance work load: the circuit-breaker avoids the need to<br />

replace blown fuses and the necessity <strong>of</strong> maintaining a stock (<strong>of</strong> different sizes and<br />

types)<br />

b Better continuity performance: the <strong>installation</strong> can be re-energized immediately<br />

following the elimination <strong>of</strong> a fault and after checking <strong>of</strong> the starter<br />

b Additional complementary devices sometimes required on a motor circuit are<br />

easily accomodated<br />

b Tripping <strong>of</strong> all three phases is assured (thereby avoiding the possibility <strong>of</strong> “single<br />

phasing”)<br />

b Full load current switching possibility (by circuit-breaker) in the event <strong>of</strong> contactor<br />

failure, e.g. contact welding<br />

b Interlocking<br />

b Diverse remote indications<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008