F - Protection against electric shock<br />

(1) On systems where the neutral is distributed, as shown in<br />

Figure F56.<br />

7 Implementation <strong>of</strong> the IT system<br />

The basic feature <strong>of</strong> the IT earthing system is that, in the event <strong>of</strong> a short-circuit to<br />

earth fault, the system can continue to operate without interruption. Such a fault is<br />

referred to as a “first fault”.<br />

In this system, all exposed conductive parts <strong>of</strong> an <strong>installation</strong> are connected via<br />

PE conductors to an earth electrode at the <strong>installation</strong>, while the neutral point <strong>of</strong> the<br />

supply transformer is:<br />

b Either isolated from earth<br />

b Or connected to earth through a high resistance (commonly 1,000 ohms or more)<br />

This means that the current through an earth fault will be measured in milli-amps,<br />

which will not cause serious damage at the fault position, or give rise to dangerous<br />

touch voltages, or present a fire hazard. The system may therefore be allowed to<br />

operate normally until it is convenient to isolate the faulty section for repair work. This<br />

enhances continuity <strong>of</strong> service.<br />

In practice, the system earthing requires certain specific measures for its satisfactory<br />

exploitation:<br />

b Permanent monitoring <strong>of</strong> the insulation with respect to earth, which must signal<br />

(audibly or visually) the occurrence <strong>of</strong> the first fault<br />

b A device for limiting the voltage which the neutral point <strong>of</strong> the supply transformer<br />

can reach with respect to earth<br />

b A “first-fault” location routine by an efficient maintenance staff. Fault location is<br />

greatly facilitated by automatic devices which are currently available<br />

b Automatic high-speed tripping <strong>of</strong> appropriate circuit-breakers must take place in<br />

the event <strong>of</strong> a “second fault” occurring before the first fault is repaired. The second<br />

fault (by definition) is an earth fault affecting a different live conductor than that <strong>of</strong> the<br />

first fault (can be a phase or neutral conductor) (1) .<br />

The second fault results in a short-circuit through the earth and/or through<br />

PE bonding conductors.<br />

7.1 Preliminary conditions (see Fig. F51 and Fig. F52)<br />

Minimum functions required Components and devices Examples<br />

Protection against overvoltages (1) Voltage limiter Cardew C<br />

at power frequency<br />

Neutral earthing resistor (2) Resistor Impedance Zx<br />

(for impedance earthing variation)<br />

Overall earth-fault monitor (3) Permanent insulation Vigilohm TR22A<br />

with alarm for first fault condition monitor PIM with alarm feature or XM 200<br />

Automatic fault clearance (4) Four-pole circuit-breakers Compact circuit-breaker<br />

on second fault and (if the neutral is distributed) or RCD-MS<br />

protection <strong>of</strong> the neutral all 4 poles trip<br />

conductor against overcurrent<br />

Location <strong>of</strong> first fault (5) With device for fault-location Vigilohm system<br />

on live system, or by successive<br />

opening <strong>of</strong> circuits<br />

Fig. F51 : Essential functions in IT schemes and examples with Merlin Gerin products<br />

HV/LV<br />

2 1 3<br />

Fig. F52 : Positions <strong>of</strong> essential functions in 3-phase 3-wire IT-earthed system<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />