F42<br />

© Schneider Electric - all rights reserved<br />

F - Protection against electric shock<br />

a b<br />

In<br />

In1<br />

Fig. F75 : Residual current circuit-breakers (RCCBs)<br />

In<br />

In1 In2 In3 In4<br />

Choice <strong>of</strong> characteristics <strong>of</strong> a residual-current circuit-breaker<br />

(RCCB - IEC 61008)<br />

Rated current<br />

The rated current <strong>of</strong> a RCCB is chosen according to the maximum sustained load<br />

current it will carry.<br />

b If the RCCB is connected in series with, and downstream <strong>of</strong> a circuit-breaker, the<br />

rated current <strong>of</strong> both items will be the same, i.e. Ιn u Ιn1 (1) (see Fig. F75a)<br />

b If the RCCB is located upstream <strong>of</strong> a group <strong>of</strong> circuits, protected by circuitbreakers,<br />

as shown in Figure F75b, then the RCCB rated current will be given by:<br />

Ιn u ku x ks (Ιn1 + Ιn2 + Ιn3 + Ιn4)<br />

Circuit-breaker and RCCB association – maxi Ιsc (r.m.s) value in kA<br />

Electrodynamic withstand requirements<br />

Protection against short-circuits must be provided by an upstream SCPD (Short-<br />

Circuit Protective Device) but it is considered that where the RCCB is located in the<br />

same distribution box (complying with the appropriate standards) as the downstream<br />

circuit-breakers (or fuses), the short-circuit protection afforded by these (outgoingcircuit)<br />

SCPDs is an adequate alternative. Coordination between the RCCB and the<br />

SCPDs is necessary, and manufacturers generally provide tables associating RCCBs<br />

and circuit-breakers or fuses (see Fig. F76).<br />

Upstream circuit-breaker DT40 DT40N C60N C60H C60L C120N C120H NG125N NG125H<br />

Downstream 2P I 20A 6.5 6.5 6.5 6.5 6.5 3 4.5 4.5 4.5<br />

RCCB 230V IN-A 40A 6 10 20 30 30 10 10 15 15<br />

IN-A 63A 6 10 20 30 30 10 10 15 15<br />

I 100A 15 15 15 15<br />

4P I 20A 4.5 4.5 4.5 4.5 4.5 2 3 3 3<br />

400V IN-A 40A 6 10 10 15 15 7 7 15 15<br />

IN-A 63A 6 10 10 15 15 7 7 15 15<br />

NG 125NA 10 16 25 50<br />

Fuses and RCCB association – maxi Ιsc (r.m.s) value in kA<br />

gG upstream fuse 20A 63A 100A 125A<br />

Downstream 2P I 20A 8<br />

RCCB 230V IN-A 40A 30 20<br />

IN-A 63A 30 20<br />

I 100A 6<br />

4P I 20A 8<br />

400V IN-A 40A 30 20<br />

IN-A 63A 30 20<br />

NG 125NA 50<br />

Fig. F76 : Typical manufacturers coordination table for RCCBs, circuit-breakers, and fuses (Merlin Gerin products)<br />

8 Residual current devices (RCDs)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008