D18<br />

© Schneider Electric - all rights reserved<br />

D - MV & LV architecture selection guide<br />

6 Choice <strong>of</strong> architecture<br />

fundamentals<br />

6.4 Number <strong>of</strong> MV/LV transformers<br />

Main characteristics to consider to determine the number <strong>of</strong> transformers:<br />

b Surface <strong>of</strong> building or site<br />

b Total power <strong>of</strong> the installed loads<br />

b Sensitivity <strong>of</strong> circuits to power interruptions<br />

b Sensitivity <strong>of</strong> circuits to disturbances<br />

b Installation scalability<br />

The basic preferred configuration comprises a single transformer supplying the total<br />

power <strong>of</strong> the installed loads. Certain factors contribute to increasing the number <strong>of</strong><br />

transformers (> 1), preferably <strong>of</strong> equal power:<br />

b A high total installed power (> 1250kVA): practical limit <strong>of</strong> unit power<br />

(standardization, ease <strong>of</strong> replacement, space requirement, etc),<br />

b A large surface area (> 5000m²): the setting up <strong>of</strong> several transformers as close as<br />

possible to the distributed loads allows the length <strong>of</strong> LV trunking to be reduced<br />

b A need for partial redundancy (down-graded operation possible in the case <strong>of</strong> a<br />

transformer failure) or total redundancy (normal operation ensured in the case a<br />

transformer failure)<br />

b Separating <strong>of</strong> sensitive and disturbing loads (e.g.: IT, motors)<br />

6.5 MV back-up generator<br />

Main characteristics to consider for the implementation <strong>of</strong> an MV back-up generator:<br />

b Site activity<br />

b Total power <strong>of</strong> the installed loads<br />

b Sensitivity <strong>of</strong> circuits to power interruptions<br />

b Availability <strong>of</strong> the public distribution network<br />

The preferred basic configuration does not include an MV generator. Certain factors<br />

contribute to installing an MV generator:<br />

b Site activity: process with co-generation, optimizing the energy bill,<br />

b Low availability <strong>of</strong> the public distribution network.<br />

Installation <strong>of</strong> a back-up generator can also be carried out at LV level.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008