14.11.2012 Views

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

G42<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

(1) Harmonics <strong>of</strong> order 3 and multiple <strong>of</strong> 3<br />

I 1 H1<br />

Fig. G63a : Triplen harmonics are in phase and cumulate in the Neutral<br />

7 The neutral conductor<br />

The c.s.a. and the protection <strong>of</strong> the neutral conductor, apart from its current-carrying<br />

requirement, depend on several factors, namely:<br />

b The type <strong>of</strong> earthing system, TT, TN, etc.<br />

b The harmonic currents<br />

b The method <strong>of</strong> protection against indirect contact hazards according to the<br />

methods described below<br />

The color <strong>of</strong> the neutral conductor is statutorily blue. PEN conductor, when insulated,<br />

shall be marked by one <strong>of</strong> the following methods :<br />

b Green-and-yellow throughout its length with, in addition, light blue markings at the<br />

terminations, or<br />

b Light blue throughout its length with, in addition, green-and-yellow markings at the<br />

terminations<br />

7.1 Sizing the neutral conductor<br />

Influence <strong>of</strong> the type <strong>of</strong> earthing system<br />

TT and TN-S schemes<br />

b Single-phase circuits or those <strong>of</strong> c.s.a. y 16 mm 2 (copper) 25 mm 2 (aluminium): the<br />

c.s.a. <strong>of</strong> the neutral conductor must be equal to that <strong>of</strong> the phases<br />

b Three-phase circuits <strong>of</strong> c.s.a. > 16 mm 2 copper or 25 mm 2 aluminium: the c.s.a. <strong>of</strong><br />

the neutral may be chosen to be:<br />

v Equal to that <strong>of</strong> the phase conductors, or<br />

v Smaller, on condition that:<br />

- The current likely to flow through the neutral in normal conditions is less than the<br />

permitted value Iz. The influence <strong>of</strong> triplen (1) harmonics must be given particular<br />

consideration or<br />

- The neutral conductor is protected against short-circuit, in accordance with the<br />

following Sub-clause G-7.2<br />

- The size <strong>of</strong> the neutral conductor is at least equal to 16 mm 2 in copper or 25 mm 2 in<br />

aluminium<br />

TN-C scheme<br />

The same conditions apply in theory as those mentioned above, but in practice,<br />

the neutral conductor must not be open-circuited under any circumstances since<br />

it constitutes a PE as well as a neutral conductor (see Figure G58 “c.s.a. <strong>of</strong> PEN<br />

conductor” column).<br />

IT scheme<br />

In general, it is not recommended to distribute the neutral conductor, i.e. a 3-phase<br />

3-wire scheme is preferred. When a 3-phase 4-wire <strong>installation</strong> is necessary,<br />

however, the conditions described above for TT and TN-S schemes are applicable.<br />

Influence <strong>of</strong> harmonic currents<br />

Effects <strong>of</strong> triplen harmonics<br />

Harmonics are generated by the non-linear loads <strong>of</strong> the <strong>installation</strong> (computers,<br />

fluorescent lighting, rectifiers, power electronic choppers) and can produce high<br />

currents in the Neutral. In particular triplen harmonics <strong>of</strong> the three Phases have a<br />

tendency to cumulate in the Neutral as:<br />

b Fundamental currents are out-<strong>of</strong>-phase by 2π/3 so that their sum is zero<br />

b On the other hand, triplen harmonics <strong>of</strong> the three Phases are always positioned in<br />

the same manner with respect to their own fundamental, and are in phase with each<br />

other (see Fig. G63a).<br />

+<br />

I 1 H3<br />

I 2 H1 + I 2 H3<br />

I 3 H1<br />

I N =<br />

3<br />

1<br />

I k H1<br />

+<br />

+<br />

I 3 H3<br />

I k H3<br />

0 + 3<br />

IH3 Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

3<br />

1

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!