M - Harmonic management<br />

I r<br />

I s<br />

I t<br />

I n<br />

Load<br />

Load<br />

Load<br />

Fig. M10 : Flow <strong>of</strong> currents in the various conductors<br />

connected to a three-phase source<br />

4 Main effects <strong>of</strong> harmonics in<br />

<strong>installation</strong>s<br />

Neutral conductors<br />

Consider a system made up <strong>of</strong> a balanced three-phase source and three identical<br />

single-phase loads connected between the phases and the neutral (see Fig. M10).<br />

Figure M11 shows an example <strong>of</strong> the currents flowing in the three phases and the<br />

resulting current in the neutral conductor.<br />

In this example, the current in the neutral conductor has an rms value that is higher<br />

than the rms value <strong>of</strong> the current in a phase by a factor equal to the square root <strong>of</strong> 3.<br />

The neutral conductor must therefore be sized accordingly.<br />

Ir<br />

Is<br />

It<br />

In<br />

(A)<br />

Fig. M11 : Example <strong>of</strong> the currents flowing in the various conductors connected to a three-phase<br />

load (In = Ir + Is + It)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

0<br />

20 40<br />

4.4 Disturbances affecting sensitive loads<br />

Effects <strong>of</strong> distortion in the supply voltage<br />

t<br />

t<br />

t<br />

t<br />

t (ms)<br />

Distortion <strong>of</strong> the supply voltage can disturb the operation <strong>of</strong> sensitive devices:<br />

b Regulation devices (temperature)<br />

b Computer hardware<br />

b Control and monitoring devices (protection relays)<br />

Distortion <strong>of</strong> telephone signals<br />

Harmonics cause disturbances in control circuits (low current levels). The level <strong>of</strong><br />

distortion depends on the distance that the power and control cables run in parallel,<br />

the distance between the cables and the frequency <strong>of</strong> the harmonics.<br />

M9<br />