14.11.2012 Views

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

G40<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

These conductors must be sized according to<br />

national practices<br />

6 Protective earthing conductor<br />

(PE)<br />

6.3 Protective conductor between MV/LV transformer<br />

and the main general distribution board (MGDB)<br />

All phase and neutral conductors upstream <strong>of</strong> the main incoming circuit-breaker<br />

controlling and protecting the MGDB are protected by devices at the MV side <strong>of</strong> the<br />

transformer. The conductors in question, together with the PE conductor, must be<br />

dimensioned accordingly. Dimensioning <strong>of</strong> the phase and neutral conductors from<br />

the transformer is exemplified in Sub-clause 7.5 <strong>of</strong> this chapter (for circuit C1 <strong>of</strong> the<br />

system illustrated in Fig. G65).<br />

Recommended conductor sizes for bare and insulated PE conductors from the<br />

transformer neutral point, shown in Figure G60, are indicated below in Figure G61.<br />

The kVA rating to consider is the sum <strong>of</strong> all (if more than one) transformers<br />

connected to the MGDB.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

PE<br />

Main earth bar<br />

for the LV <strong>installation</strong><br />

Fig. G60 : PE conductor to the main earth bar in the MGDB<br />

MGDB<br />

The table indicates the c.s.a. <strong>of</strong> the conductors in mm 2 according to:<br />

b The nominal rating <strong>of</strong> the MV/LV transformer(s) in kVA<br />

b The fault-current clearance time by the MV protective devices, in seconds<br />

b The kinds <strong>of</strong> insulation and conductor materials<br />

If the MV protection is by fuses, then use the 0.2 seconds columns.<br />

In IT schemes, if an overvoltage protection device is installed (between the<br />

transformer neutral point and earth) the conductors for connection <strong>of</strong> the device<br />

should also be dimensioned in the same way as that described above for<br />

PE conductors.<br />

Transformer Conductor Bare PVC-insulated XLPE-insulated<br />

rating in kVA material conductors conductors conductors<br />

(230/400 V Copper t(s) 0.2 0.5 - 0.2 0.5 - 0.2 0.5 -<br />

output) Aluminium t(s) - 0.2 0.5 - 0.2 0.5 - 0.2 0.5<br />

y100 c.s.a. <strong>of</strong> PE 25 25 25 25 25 25 25 25 25<br />

160 conductors 25 25 35 25 25 50 25 25 35<br />

200 SPE (mm 2 ) 25 35 50 25 35 50 25 25 50<br />

250 25 35 70 35 50 70 25 35 50<br />

315 35 50 70 35 50 95 35 50 70<br />

400 50 70 95 50 70 95 35 50 95<br />

500 50 70 120 70 95 120 50 70 95<br />

630 70 95 150 70 95 150 70 95 120<br />

800 70 120 150 95 120 185 70 95 150<br />

1,000 95 120 185 95 120 185 70 120 150<br />

1,250 95 150 185 120 150 240 95 120 185<br />

Fig. G61 : Recommended c.s.a. <strong>of</strong> PE conductor between the MV/LV transformer and the MGDB,<br />

as a function <strong>of</strong> transformer ratings and fault-clearance times.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!