G - Sizing and protection <strong>of</strong> conductors<br />

Fig. G10 : Examples <strong>of</strong> methods <strong>of</strong> <strong>installation</strong> (part <strong>of</strong> table 52-3 <strong>of</strong> IEC 60364-5-52) (continued on next page)<br />

2 Practical method for determining<br />

the smallest allowable crosssectional<br />

area <strong>of</strong> circuit conductors<br />

Examples <strong>of</strong> wiring systems and reference methods <strong>of</strong><br />

<strong>installation</strong>s<br />

An illustration <strong>of</strong> some <strong>of</strong> the many different wiring systems and methods <strong>of</strong><br />

<strong>installation</strong> is provided in Figure G10.<br />

Several reference methods are defined (with code letters A to G), grouping<br />

<strong>installation</strong> methods having the same characteristics relative to the current-carrying<br />

capacities <strong>of</strong> the wiring systems.<br />

Item No. Methods <strong>of</strong> <strong>installation</strong> Description Reference method <strong>of</strong><br />

<strong>installation</strong> to be used to<br />

obtain current-carrying<br />

capacity<br />

1 Insulated conductors or single-core<br />

cables in conduit in a thermally<br />

insulated wall<br />

A1<br />

Room<br />

2 Multi-core cables in conduit in a A2<br />

thermally insulated wall<br />

4 Insulated conductors or single-core B1<br />

cables in conduit on a wooden, or<br />

masonry wall or spaced less than<br />

0,3 x conduit diameter from it<br />

5 Multi-core cable in conduit on a B2<br />

wooden, or mansonry wall or spaced<br />

less than 0,3 x conduit diameter<br />

from it<br />

20 Single-core or multi-core cables: C<br />

- fixed on, or sapced less than 0.3 x cable<br />

diameter from a wooden wall<br />

30 On unperforated tray C<br />

0.3 De<br />

0.3 De<br />

Room<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G9<br />

© Schneider Electric - all rights reserved