J - Protection against voltage surges in LV<br />

1<br />

Equipment to be<br />

protected<br />

2<br />

Determine the<br />

architecture <strong>of</strong> the<br />

building<br />

3<br />

Risk level <strong>of</strong><br />

the impact <strong>of</strong> a<br />

lightning strike<br />

Choice <strong>of</strong> type <strong>of</strong><br />

surge arrester<br />

Domestic equipment<br />

Type 2<br />

10 kA<br />

Detached house,<br />

Pr<strong>of</strong>essional<br />

premises<br />

Type 2<br />

40 kA<br />

Type 1<br />

25 kA<br />

+<br />

Type 2<br />

40 kA<br />

Audio-video, computers,<br />

household appliances,<br />

burglar alarm, etc.<br />

Type 1<br />

25 kA<br />

+<br />

Type 2<br />

40 kA<br />

Apartment, small<br />

semi-detached<br />

house<br />

Type 2<br />

10 kA<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Communal part <strong>of</strong> a<br />

building<br />

Note:<br />

Type 1: very high discharge capacity surge arrester used with a lightning conductor with an impact level <strong>of</strong> and .<br />

Type 2: surge arrester used in cascade behind a type 1 surge arrester or alone in zone and .<br />

Fig. J32 : Domestic equipment<br />

Lightning also propagates through<br />

telecommunications networks.<br />

It can damage all the equipment connected to<br />

these networks.<br />

4 Choosing a protection device<br />

Type 2<br />

40 kA<br />

Protection <strong>of</strong> telecommunications equipment<br />

Type 2<br />

65 kA<br />

Choice <strong>of</strong> surge arresters PRC<br />

Analogue telephone networks < 200 V b<br />

Type 1<br />

25 kA<br />

+<br />

Type 2<br />

40 kA<br />

Type 1<br />

25 kA<br />

+<br />

Type 2<br />

40 kA<br />

J19<br />

© Schneider Electric - all rights reserved