14.11.2012 Views

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

F - Protection against electric shock<br />

Fig. F59 : Fire-risk location<br />

2 y I rm y 4I n<br />

Great length <strong>of</strong> cable<br />

PE<br />

Fig. F60 : A circuit-breaker with low-set instantaneous<br />

magnetic trip<br />

Fire-risk<br />

location<br />

Phases<br />

Neutral<br />

PE<br />

7 Implementation <strong>of</strong> the IT system<br />

7.4 Protection in high fire-risk locations<br />

Protection by a RCD <strong>of</strong> sensitivity y 500 mA at the origin <strong>of</strong> the circuit supplying the<br />

fire-risk locations is mandatory in some countries (see Fig. F59).<br />

A preferred sensitivity <strong>of</strong> 300 mA may be adopted.<br />

7.5 When the fault current-loop impedance is<br />

particularly high<br />

When the earth-fault current is restricted due to an inevitably high fault-loop<br />

impedance, so that the overcurrent protection cannot be relied upon to trip the circuit<br />

within the prescribed time, the following possibilities should be considered:<br />

Suggestion 1 (see Fig. F60)<br />

b Install a circuit-breaker which has an instantaneous magnetic tripping element with<br />

an operation level which is lower than the usual setting, for example:<br />

2In y Irm y 4In<br />

This affords protection for persons on circuits which are abnormally long. It must<br />

be checked, however, that high transient currents such as the starting currents <strong>of</strong><br />

motors will not cause nuisance trip-outs.<br />

b Schneider Electric solutions<br />

v Type G Compact (2Im y Irm y 4Im)<br />

v Type B Multi 9 circuit-breaker<br />

Suggestion 2 (see Fig. F61)<br />

Install a RCD on the circuit. The device does not need to be highly-sensitive (HS)<br />

(several amps to a few tens <strong>of</strong> amps). Where socket-outlets are involved, the<br />

particular circuits must, in any case, be protected by HS (y 30 mA) RCDs; generally<br />

one RCD for a number <strong>of</strong> socket outlets on a common circuit.<br />

b Schneider Electric solutions<br />

v RCD Multi 9 NG125 : ΙΔn = 1 or 3 A<br />

v Vigicompact REH or REM: ΙΔn = 3 to 30 A<br />

Fig. F61 : RCD protection Fig. F62 : Improved equipotential bonding<br />

Suggestion 3<br />

Increase the size <strong>of</strong> the PE conductors and/or the phase conductors, to reduce the<br />

loop impedance.<br />

Suggestion 4 (see Fig. F62)<br />

Add supplementary equipotential conductors. This will have a similar effect to that<br />

<strong>of</strong> suggestion 3, i.e. a reduction in the earth-fault-loop resistance, while at the same<br />

time improving the existing touch-voltage protection measures. The effectiveness<br />

<strong>of</strong> this improvement may be checked by a resistance test between each exposed<br />

conductive part and the local main protective conductor.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

F35<br />

© Schneider Electric - all rights reserved

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!