14.11.2012 Views

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

G44<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

7 The neutral conductor<br />

Examples<br />

Consider a three-phase circuit with a <strong>design</strong> load <strong>of</strong> 37 A to be installed using fourcore<br />

PVC insulated cable clipped to a wall, <strong>installation</strong> method C. From Figure G24,<br />

a 6 mm 2 cable with copper conductors has a current-carrying capacity <strong>of</strong> 40 A and<br />

hence is suitable if harmonics are not present in the circuit.<br />

b If 20 % third harmonic is present, then a reduction factor <strong>of</strong> 0,86 is applied and the<br />

<strong>design</strong> load becomes: 37/0.86 = 43 A.<br />

For this load a 10 mm 2 cable is necessary.<br />

b If 40 % third harmonic is present, the cable size selection is based on the neutral<br />

current which is: 37 x 0,4 x 3 = 44,4 A and a reduction factor <strong>of</strong> 0,86 is applied,<br />

leading to a <strong>design</strong> load <strong>of</strong>: 44.4/0.86 = 51.6 A.<br />

For this load a 10 mm 2 cable is suitable.<br />

b If 50 % third harmonic is present, the cable size is again selected on the basis <strong>of</strong><br />

the neutral current, which is: 37 x 0,5 x 3 = 55,5 A .In this case the rating factor is<br />

1 and a 16 mm 2 cable is required.<br />

7.2 Protection <strong>of</strong> the neutral conductor<br />

(see Fig. G64 next page)<br />

Protection against overload<br />

If the neutral conductor is correctly sized (including harmonics), no specific<br />

protection <strong>of</strong> the neutral conductor is required because it is protected by the phase<br />

protection.<br />

However, in practice, if the c.s.a. <strong>of</strong> the neutral conductor is lower than the phase<br />

c.s.a, a neutral overload protection must be installed.<br />

Protection against short-circuit<br />

If the c.s.a. <strong>of</strong> the neutral conductor is lower than the c.s.a. <strong>of</strong> the phase conductor,<br />

the neutral conductor must be protected against short-circuit.<br />

If the c.s.a. <strong>of</strong> the neutral conductor is equal or greater than the c.s.a. <strong>of</strong> the phase<br />

conductor, no specific protection <strong>of</strong> the neutral conductor is required because it is<br />

protected by the phase protection.<br />

7.3 Breaking <strong>of</strong> the neutral conductor<br />

(see Fig. G64 next page)<br />

The need to break or not the neutral conductor is related to the protection against<br />

indirect contact.<br />

In TN-C scheme<br />

The neutral conductor must not be open-circuited under any circumstances since it<br />

constitutes a PE as well as a neutral conductor.<br />

In TT, TN-S and IT schemes<br />

In the event <strong>of</strong> a fault, the circuit-breaker will open all poles, including the neutral<br />

pole, i.e. the circuit-breaker is omnipolar.<br />

The action can only be achieved with fuses in an indirect way, in which the operation<br />

<strong>of</strong> one or more fuses triggers a mechanical trip-out <strong>of</strong> all poles <strong>of</strong> an associated<br />

series-connected load-break switch.<br />

7.4 Isolation <strong>of</strong> the neutral conductor<br />

(see Fig. G64 next page)<br />

It is considered to be the good practice that every circuit be provided with the means<br />

for its isolation.<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!