14.11.2012 Views

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

M - Harmonic management<br />

3 <strong>General</strong><br />

Fig. M3 : Installation supplying a non-linear load, where only the phenomena concerning the<br />

50 Hz frequency (fundamental frequency) are shown<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

Z h<br />

Z l<br />

I 50 Hz<br />

Non-linear<br />

load<br />

Fig. M4 : Same <strong>installation</strong>, where only the phenomena concerning the frequency <strong>of</strong> harmonic<br />

order h are shown<br />

V h<br />

I h<br />

Non-linear<br />

load<br />

V h = Harmonic voltage<br />

= Z h x I h<br />

Supply <strong>of</strong> the non-linear load creates the flow <strong>of</strong> a current I 50Hz (shown in<br />

figure M3), to which is added each <strong>of</strong> the harmonic currents Ih (shown in figure M4),<br />

corresponding to each harmonic order h.<br />

Still considering that the loads reinject harmonic current upstream into the<br />

distribution network, it is possible to create a diagram showing the harmonic currents<br />

in the network (see Fig. M ).<br />

Backup power<br />

supply<br />

G<br />

Power-factor<br />

correction<br />

MV/LV<br />

Harmonic<br />

disturbances to<br />

distribution network<br />

and other users<br />

A<br />

Ih a<br />

Ih b<br />

Ih d<br />

Ih e<br />

(do not create<br />

harmonics)<br />

Rectifier<br />

Arc furnace<br />

Welding machine<br />

Variable-speed drive<br />

Fluorescent or<br />

discharge lamps<br />

Devices drawing rectified<br />

current (televisions,<br />

computer hardware, etc.)<br />

Linear loads<br />

Note in the diagram that though certain loads create harmonic currents in the distribution<br />

network, other loads can absorb the harmonic currents.<br />

Fig. M5 : Flow <strong>of</strong> harmonic currents in a distribution network<br />

Harmonics have major economic effects in <strong>installation</strong>s:<br />

b Increases in energy costs<br />

b Premature ageing <strong>of</strong> equipment<br />

b Production losses<br />

M<br />

© Schneider Electric - all rights reserved