G - Sizing and protection <strong>of</strong> conductors<br />

2 Practical method for determining<br />

the smallest allowable crosssectional<br />

area <strong>of</strong> circuit conductors<br />

Figure G1 gives the values <strong>of</strong> correction factor k 4 for different configurations <strong>of</strong><br />

unburied cables or conductors, for groups <strong>of</strong> more than one circuit <strong>of</strong> single-core<br />

cables in free air.<br />

Method <strong>of</strong> <strong>installation</strong> Number Number <strong>of</strong> three-phase Use as a<br />

<strong>of</strong> tray circuits multiplier to<br />

rating for<br />

1 2 3<br />

Perforated 31 Touching 1 0.98 0.91 0.87 Three cables in<br />

trays horizontal<br />

2 0.96 0.87 0.81 formation<br />

20 mm<br />

3 0.95 0.85 0.78<br />

Vertical 31 Touching 1 0.96 0.86 Three cables in<br />

perforated vertical<br />

trays<br />

225 mm<br />

2 0.95 0.84 formation<br />

Ladder 32 1 1.00 0.97 0.96 Three cables in<br />

supports, Touching<br />

horizontal<br />

cleats, etc... 33 2 0.98 0.93 0.89 formation<br />

34 3 0.97 0.90 0.86<br />

20 mm<br />

Perforated<br />

trays<br />

31<br />

2De<br />

De 1 1.00 0.98 0.96 Three cables in<br />

trefoil formation<br />

2 0.97 0.93 0.89<br />

20 mm<br />

3 0.96 0.92 0.86<br />

Vertical<br />

perforated<br />

31 De<br />

Spaced 1 1.00 0.91 0.89<br />

trays<br />

225 mm<br />

2 1.00 0.90 0.86<br />

2De<br />

Ladder<br />

supports,<br />

32 2De<br />

De<br />

1 1.00 1.00 1.00<br />

cleats, etc... 33 2 0.97 0.95 0.93<br />

34 20 mm 3 0.96 0.94 0.90<br />

Fig. G17 : Reduction factors for groups <strong>of</strong> more than one circuit <strong>of</strong> single-core cables to be applied to reference rating for one circuit <strong>of</strong> single-core cables in free air<br />

- Method <strong>of</strong> <strong>installation</strong> F. (table A.52.21 <strong>of</strong> IEC 60364-5-52)<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

G13<br />

© Schneider Electric - all rights reserved