B - Connection to the MV public<br />

distribution network<br />

Walk-in Non walk-in Half buried<br />

a - b -<br />

Underground<br />

Fig. B38 : The four <strong>design</strong>s according to IEC 62271-202<br />

standard and two pictures [a] walk-in type MV/LV substation;<br />

[b] half buried type MV/LV substation<br />

6 Constitution <strong>of</strong><br />

MV/LV distribution substations<br />

Materials for operation and safety<br />

According to local safety <strong>rules</strong>, generally, the substation is provided with:<br />

b Materials for assuring safe exploitation <strong>of</strong> the equipment including:<br />

v Insulating stool and/or an insulating mat (rubber or synthetic)<br />

v A pair <strong>of</strong> insulated gloves stored in an envelope provided for the purpose<br />

v A voltage-detecting device for use on the MV equipment<br />

v Earthing attachments (according to type <strong>of</strong> switchgear)<br />

b Fire-extinguishing devices <strong>of</strong> the powder or CO2 type<br />

b Warning signs, notices and safety alarms:<br />

v On the external face <strong>of</strong> all access doors, a DANGER warning plaque and<br />

prohibition <strong>of</strong> entry notice, together with instructions for first-aid care for victims <strong>of</strong><br />

<strong>electrical</strong> accidents.<br />

6.3 Outdoor substations<br />

Outdoor substation with prefabricated enclosures<br />

A prefabricated MV/LV substation complying with IEC 62271-202 standard includes :<br />

b equipement in accordance with IEC standards<br />

b a type tested enclosure, which means during its <strong>design</strong>, it has undergone a battery<br />

<strong>of</strong> tests (see Fig. B37):<br />

v Degree <strong>of</strong> protection<br />

v Functional tests<br />

v Temperature class<br />

v Non-flammable materials<br />

v Mechanical resistance <strong>of</strong> the enclosure<br />

v Sound level<br />

v Insulation level<br />

v Internal arc withstand<br />

v Earthing circuit test<br />

v Oil retention,…<br />

Use <strong>of</strong> equipment conform<br />

to IEC standards:<br />

b Degree <strong>of</strong> protection<br />

b Electromagnetic<br />

compatibility<br />

b Functional tests<br />

b Temperature class<br />

b Non-flammable<br />

materials<br />

Fig. B37 : Type tested substation according to IEC 62271-202 standard<br />

Main benefits are :<br />

b Safety:<br />

v For public and operators thanks to a high reproducible quality level<br />

b Cost effective:<br />

v Manufactured, equipped and tested in the factory<br />

b Delivery time<br />

v Delivered ready to be connected.<br />

IEC 62271-202 standard includes four main <strong>design</strong>s (see Fig. B38)<br />

b Walk-in type substation :<br />

v Operation protected from bad weather conditions<br />

b Non walk-in substation<br />

v Ground space savings, and outdoors operations<br />

b Half buried substation<br />

v Limited visual impact<br />

b Underground substation<br />

v Blends completely into the environment.<br />

LV<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

MV<br />

Earthing circuit test Oil retention<br />

Mechanical resistance<br />

<strong>of</strong> the enclosure:<br />

b Sound level<br />

b Insulation level<br />

b Internal arcing<br />

withstand<br />

B39<br />

© Schneider Electric - all rights reserved