14.11.2012 Views

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

Chapter A General rules of electrical installation design

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

G32<br />

© Schneider Electric - all rights reserved<br />

G - Sizing and protection <strong>of</strong> conductors<br />

In practice this means that the length <strong>of</strong> circuit<br />

downstream <strong>of</strong> the protective device must not<br />

exceed a calculated maximum length:<br />

0.8 U Sph<br />

Lmax<br />

=<br />

2ρI m<br />

(1) For larger c.s.a.’s, the resistance calculated for the<br />

conductors must be increased to account for the non-uniform<br />

current density in the conductor (due to “skin” and “proximity”<br />

effects)<br />

Suitable values are as follows:<br />

150 mm 2 : R + 15%<br />

185 mm 2 : R + 20%<br />

240 mm 2 : R + 25%<br />

300 mm 2 : R + 30%<br />

(2) Or for aluminium according to conductor material<br />

(3) The high value for resistivity is due to the elevated<br />

temperature <strong>of</strong> the conductor when passing short-circuit<br />

current<br />

5 Particular cases <strong>of</strong> short-circuit<br />

current<br />

Practical method <strong>of</strong> calculating Lmax<br />

The limiting effect <strong>of</strong> the impedance <strong>of</strong> long circuit conductors on the value <strong>of</strong><br />

short-circuit currents must be checked and the length <strong>of</strong> a circuit must be restricted<br />

accordingly.<br />

The method <strong>of</strong> calculating the maximum permitted length has already been<br />

demonstrated in TN- and IT- earthed schemes for single and double earth faults,<br />

respectively (see <strong>Chapter</strong> F Sub-clauses 6.2 and 7.2). Two cases are considered<br />

below:<br />

1 - Calculation <strong>of</strong> L max for a 3-phase 3-wire circuit<br />

The minimum short-circuit current will occur when two phase wires are shortcircuited<br />

at the remote end <strong>of</strong> the circuit (see Fig. G46).<br />

Schneider Electric - Electrical <strong>installation</strong> guide 2008<br />

P<br />

0.8 U<br />

Fig G46 : Definition <strong>of</strong> L for a 3-phase 3-wire circuit<br />

L<br />

Load<br />

Using the “conventional method”, the voltage at the point <strong>of</strong> protection P is assumed<br />

to be 80% <strong>of</strong> the nominal voltage during a short-circuit fault, so that 0.8 U = Isc Zd,<br />

where:<br />

Zd = impedance <strong>of</strong> the fault loop<br />

Isc = short-circuit current (ph/ph)<br />

U = phase-to-phase nominal voltage<br />

For cables y 120 mm2 , reactance may be neglected, so that<br />

2L<br />

Zd = ρ (1)<br />

Sph<br />

where:<br />

ρ = resistivity <strong>of</strong> copper (2) at the average temperature during a short-circuit,<br />

Sph = c.s.a. <strong>of</strong> a phase conductor in mm 2<br />

L = length in metres<br />

The condition for the cable protection is Im y Isc with Im = magnetic trip current<br />

setting <strong>of</strong> the CB.<br />

This leads to Im y<br />

0.8 U<br />

which gives L y 0.8 U Sph<br />

Zd<br />

Lmax<br />

=<br />

2ρI m<br />

with U = 400 V<br />

ρ = 1.25 x 0.018 = 0.023 Ω.mm 2 /m (3)<br />

Lmax = maximum circuit length in metres<br />

k Sph<br />

L<br />

m<br />

max = I<br />

2 - Calculation <strong>of</strong> Lmax for a 3-phase 4-wire 230/400 V circuit<br />

The minimum Isc will occur when the short-circuit is between a phase conductor and<br />

the neutral.<br />

A calculation similar to that <strong>of</strong> example 1 above is required, but using the following<br />

formulae (for cable y 120 mm2 (1) ).<br />

b Where Sn for the neutral conductor = Sph for the phase conductor<br />

3,333 Sph<br />

Lmax<br />

=<br />

Im<br />

b If Sn for the neutral conductor < Sph, then<br />

L 6,666 Sph 1<br />

max =<br />

where m =<br />

Im<br />

1+ m<br />

Sph<br />

Sn<br />

For larger c.s.a.’s than those listed, reactance values must be combined with those <strong>of</strong><br />

resistance to give an impedance. Reactance may be taken as 0.08 mΩ/m for cables<br />

(at 50 Hz). At 60 Hz the value is 0.096 mΩ/m.

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!