MAY 2009SOLICITATION FOR OFFERS OUTPATIENT CLINIC <strong>SFO</strong> NO. VA-101-XX-RP-XXXX[INSERT LOCATION OF FACILITY]D. Telecommunications OutletsOutlet boxes shall be the same minimum size as NEC standard quadraplex (or dual duplex)electrical outlet boxes.Outlet boxes shall be equipped with full covered wall faceplates and two (2) each modularCategory Six RJ-45 jacks and contain enough space for two (2) each additional modularCategory Six RJ-45 jacks, one additional modular (1) stainless steel fiber-optic, and one (1)BNC (A/E note: an "F" type may be substituted "depending on system design) with analogcoax cable jacks (for a total <strong>of</strong> six available modular jack positions). For cable installed insystems furniture route cables through raceways internal to the furniture frame to the outlet ateach workstation.Unless otherwise specified, mounting heights for telecommunication outlets shall be:Telecommunications Outlets Mounting HeightAREA/FUNCTION MOUNTING REQUIREMENTSPay station4 ft [1,200 mm] above finishedfloor (AFF)Desk outletSpecial Use Areas1.5 ft [450 mm] AFFAs required by designPatient Bed Prefabricated Wall Units (PBPU): Use the provided receptacle box, conduit andconnections. The PBPU UL listing shall not be violated. The Lessor is responsible to restoreeach unit’s violated UL to the OEM standard at the Lessor’s expense.Special Systems: Provide each outlet minimum 18 in [450 mm] AFF unless otherwisespecified by system design or indicated on the drawings.Outlets shall not be located within 48 in [1200 mm] <strong>of</strong> the "swing open" side <strong>of</strong> inward openingdoors or within 18 in [450 mm] <strong>of</strong> light switches, thermostats, or other electrical receptacles.Elevator voice cables providing voice service to the elevator car shall be extended to theelevator equipment room.E. DrawingsThe A/E shall clearly show the locations <strong>of</strong> telecommunications outlets, conduit runs, cabletrays or wireways, equipment cabinets and/or racks, telecommunications rooms/backboards,terminal, junction, and/or pull boxes on the drawings.The A/E shall clearly show the exterior and/or underground raceway system, includingdistances between buildings, manholes, and in-ground pullboxes.All raceways sizes shall be indicated on the drawings.Drawings must include a detailed riser diagram for all distribution systems, and the interfacesbetween systems.Part I: Basic Solicitation Requirements – Page 129 <strong>of</strong> 196Lessor __________ Gov’t. ____________________ <strong>of</strong> __________ Pages

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!