Inspection item• Removal (<strong>FR</strong>-F740-185K or more)1) Remove a fan cover.2) After removing a fan connector, remove a fan block.3) Remove a fan.Fan *3)Fan connectionconnector2)1)* The number of cooling fans differs according to the inverter capacity.• Reinstallation (<strong>FR</strong>-F740-185K or more)1) After confirming the orientation of the fan, reinstall the fan so that the arrow on the left of "AIR FLOW" facesup.AIR FLOW2) Install fans referring to the above figure.CAUTION• Installing the fan in the opposite air flow direction can cause the inverter life to be shorter.• When installing the fan, use care to prevent wires from being caught between the inverter and fan.• Switch the power off before replacing fans. Since the inverter circuits are charged with voltage even after poweroff, replace fans only when the inverter cover is on the inverter to prevent an electric shock accident.116