4ADJUSTMENTParameter listFunction— 260 Refer to Pr.72.Decelerate the motor to a stop at instantaneous power failure—Parameter261262263264265RelatedparametersNamePower failure stopselectionSubtractedfrequency atdeceleration startSubtraction startingfrequencyPower-failuredeceleration time 1Power-failuredeceleration time 2Increments1 00.01Hz 3Hz 0 to 20Hz0.01Hz0.1/0.01s0.1/0.01sInitialValue60Hz5s9999012Range0 to 120Hz99990 to 3600/360s0 to 3600/360s266Power failuredeceleration timeswitchoverfrequency0.01Hz 60Hz 0 to 400Hz267 Refer to Pr.73.268 Refer to Pr.52.269 Parameter for manufacturer setting. Do not set.299 Refer to Pr.57, Pr. 58.DescriptionCoasting to stopWhen undervoltage or power failureoccurs, the inverter output is shut off.When undervoltage or a power failureoccurs, the inverter can be decelerated toa stop.When undervoltage or a power failure occurs,the inverter can be decelerated to a stop.If power is restored during a power failure, theinverter accelerates again.Normally operation can be performed withthe initial value unchanged. But adjust thefrequency according to the magnitude ofthe load specifications (moment of inertia,torque).When output frequency ≥ Pr.263Decelerate from the speed obtainedfrom output frequency minus Pr.262.When output frequency < Pr.263Decelerate from output frequencyDecelerate from the speed obtained fromoutput frequency minus Pr.262.Set a deceleration slope down to thefrequency set in Pr.266.◦ ◦ ◦◦ ◦ ◦◦ ◦ ◦◦ ◦ ◦Set a deceleration slope below thefrequency set in Pr.266. ◦ ◦ ◦9999 Same slope as in Pr.264Set the frequency at which thedeceleration slope is switched from thePr.264 setting to the Pr.265 setting.ParametercopyParameterclearAllparameterclear◦: enabled× : disabled◦ ◦ ◦Parameter list85
Parameter listFunctionPU connector communicationParameter331332333334335336337338339341342343Relatedparameters539RS-485communicationstation numberRS-485communicationspeedRS-485 communicationstop bit lengthRS-485 communicationparity check selectionRS-485 communicationretry countRS-485communicationcheck time intervalRS-485 communicationwaiting time settingCommunicationoperation commandsourceCommunicationspeed commandsourceRS-485 communicationCR/LF selectionCommunicationEEPROM writeselectionCommunicationerror countModbus-RTUcommunicationcheck time interval1 01 960 to 31(0 to 247)3, 6, 12, 24,48, 96, 192,3841 1 0, 1, 10, 111 2 0, 1, 21 10.1s 0s1 99991 01 00 to 10,999900.1 to999.8sSet the inverter station number.(same specifications as Pr.117 ) When "1"(Modbus-RTU protocol) is set in Pr.551, thesetting range within parenthesis is applied.Used to select the communication speed.(same specifications as Pr.118)Select stop bit length and data length.(same specifications as Pr.119)Select the parity check specifications.(same specifications as Pr.120)Set the permissible number of retries atoccurrence of a data receive error. (samespecifications as Pr.121)RS-485 communication can be made, butthe inverter will come to trip in the NEToperation mode.Set the communication check time interval.(same specifications as Pr.122)9999 No communication check0 to 150ms,9999Set the waiting time between datatransmission to the inverter and response.(same specifications as Pr.123)0 Operation command source communication1 Operation command source external0 Speed command source communication121 1 0, 1, 21 01 0 (read only)0.1s 9999549 Protocol selection 1 0550551NameNET modeoperation commandsource selectionPU mode operationcommand sourceselectionIncrementsInitialValue1 99991 20100.1 to999.8s999901Speed command source external (Frequencysetting from communication is invalid,terminal 2 and 1 setting from external is valid)Speed command source external (Frequencysetting from communication is valid, terminal2 and 1 setting from external is invalid)Select presence/absence of CR/LF.(same specifications as Pr.124)Parameter values written by communicationare written to the EEPROM and RAM.Parameter values written bycommunication are written to the RAM.Display the number of communicationerrors during Modbus-RTU communication.Read only.Displayed only when Modbus-RTUprotocol is selected.Modbus-RTU communication can bemade, but the inverter will come to trip inthe NET operation mode.Set the interval of communication check time.(same specifications as Pr. 122)No communication check (signal lossdetectiion) is made)Mitsubishi inverter(computer link)protocolModbus-RTUprotocol0 Communication option valid1 Inverter RS-485 terminal valid999912RangeDescriptionAfter setting change,reset (switch poweroff, then on) theinverter.The setting change isreflected after a reset.Automatic recognition of thecommunication optionNormally, the RS-485 terminals are valid.Communication option is valid when thecommunication option is mounted.Select the RS-485 terminals as the PUoperation mode control source.Select the PU connector as the PUoperation mode control source.ParametercopyParameterclearAllparameterclear◦: enabled× : disabled◦ ◦ ◦◦ ◦ ◦◦ ◦ ◦◦ ◦ ◦◦ ◦ ◦◦ ◦ ◦◦ ◦ ◦◦ ◦ ◦◦ ◦ ◦◦ ◦ ◦◦ ◦ ◦× × ×◦ ◦ ◦◦ ◦ ◦◦ ◦ ◦◦ ◦ ◦86