262 Chapter 7 Development Length of Reinforcing Bars<br />

and 7.5 becomes<br />

l ( ) ( )(<br />

)<br />

d 3 f y ψt ψ<br />

=<br />

e ψ s<br />

√ ( )<br />

d b 40λ f<br />

′ cb c<br />

+ K tr ∕db<br />

(7.7)<br />

where<br />

ψ t = bar location<br />

ψ e = coating factor<br />

ψ s = bar-size factor<br />

λ = lightweight aggregate concrete factor (ACI Code, Section 19.2.4.2)<br />

= 1.0 normal-weight concrete<br />

= When lightweight aggregate is used, λ shall not exceed 0.75 unless splitting tensile strength is<br />

specified, then<br />

λ = f ct ∕(6.7 √ f ′ c ) ≤ 1 (ACI Code, Section 19.2.4.2) c b = spacing or cover dimension (in.); the<br />

smaller of<br />

(1) Distance from center of bar or wire being developed to the nearest concrete surface or<br />

(2) One-half the center-to-center spacing of bars or wires being developed<br />

K tr = transverse reinforcement index<br />

= 40 A tr /sn<br />

n = number of bars or wires being developed along the plane of splitting<br />

s = maximum spacing of transverse reinforcement within l d , center to center (in.)<br />

f yt = yield strength of transverse reinforcement (psi)<br />

A tr = total sectional area of all transverse reinforcement within spacing s that crosses the potential<br />

plane of splitting through to the reinforcement being developed (in. 2 )<br />

Notes:<br />

1. Let (c b - + K tr )/d b not exceed 2.5 to safeguard against pullout-type failures.<br />

2. The value of √ f c ′ shall not exceed 100 psi (ACI Code, Section 25.4.1.4).<br />

3. Let K tr = 0 be used as a design simplification (ACI Code, Section 25.4.2.3).<br />

7.3.2 ACI Code Factors for Calculating l d for Bars in Tension<br />

1. Ψ t = bar location factor<br />

Ψ t = 1.3 for top bars defined as horizontal reinforcement, placed so that more than 12 in. of<br />

fresh concrete is below the development length, or splice<br />

Ψ t = 1.0 for all other reinforcement<br />

2. Ψ e = coating factor<br />

Ψ e = 1.5 for epoxy-coated bars or wires with cover less than 3d b or clear spacing less than<br />

6d b<br />

Ψ e = 1.2 for all other epoxy coated bars or wires<br />

Ψ e = 1.0 for uncoated and zinc-coated (galvanized) reinforcement (However, the value of the<br />

Ψ t Ψ e product should not exceed 1.7.)<br />

3. Ψ s = bar size factor<br />

Ψ s = 0.8 for no. 6 bars or smaller bars and deformed wires<br />

Ψ s = 1.0 for no. 7 bars and larger bars