24.02.2017 Views

Structural Concrete - Hassoun

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

688 Chapter 17 Design of Two-Way Slabs<br />

It can be seen that the fixed-end moment coefficient, k ′′ = 0.084, is very close to the coefficient<br />

1<br />

= 0.0833 usually used to calculate the fixed-end moments in beams. This is expected because<br />

12<br />

the part of the span that has a variable moment of inertia is very small in flat plates where no<br />

column capital or drop panels are used. In this example, only parts AB and CD, each equal to<br />

0.83 ft, have a higher moment of inertia than I s . In flat plates where the ratio of the span to column<br />

width is high, say, at least 20, the coefficient 0.0833 may be used to calculate approximately the<br />

fixed-end moments. Fixed-end moment (due to q u = 276 psf) = 0.084(0.245)(20)(25) 2 = 256 K ⋅ ft.<br />

The factors K, K s ′,andK′′ can be obtained from tables prepared by Simmonds and Misic [18] to<br />

meet the ACI requirements for the equivalent frame method.<br />

9. Moment distribution can be performed on half the frame due to symmetry. Once the end negative<br />

moments are computed, the positive moments at the center of any span can be obtained by subtracting<br />

the average value of the negative end moments from the simple beam positive moment.<br />

The moment distribution is shown in Fig. 17.39. The final bending moments and shear forces are<br />

shown in Fig. 17.40.<br />

10. Slabs can be designed for the negative moments at the face of the columns as shown in Fig. 17.40.<br />

Example 17.14 SI Units<br />

Use the direct design method to design a typical interior flat slab with drop panels to carry a dead load<br />

of 8.6 kN/m 2 and a live load of 11 kN/m 2 . The floor system consists of six panels in each direction, with<br />

a panel size of 6.0 × 5.4 m. All panels are supported by 0.4-m-diameter columns with 1.0-m-diameter<br />

column capitals. The story height is 3.0 m. Use f c ′ = 28 MPa and f y = 400 MPa.<br />

Solution<br />

1. All the ACI limitations to using the direct design method are met. Determine the minimum slab<br />

thickness, h, using Eqs. 17.1 and Eqs. 17.2. The diameter of the column capital equals 1.0 m.<br />

The equivalent square column section of the same area will have a side of √ πr 2 = √ π(500) 2 =<br />

885 mm or 900 mm.<br />

Clear span (long direction) =6.0 − 0.9 = 5.1m<br />

Clear span (short direction) =5.4 − 0.9 = 4.5m<br />

Because no beams are used α fm = 0, β s = 1.0, and β = 6.0 m/5.4 m = 1.11. From Table 17.1,<br />

minimum slab thickness h = l n /33 = 5100/33 = 155 mm, but because a drop panel is used, h may<br />

be reduced by 10% if drop panels extend a distance of at least l/6 in each direction from the<br />

centerline of support and project below the slab a distance of at least h/4. Therefore, use a slab<br />

thickness h = 0.9 × 155 = 140 mm and a drop panel length and width as follows:<br />

Long direction l 1<br />

3 = 6.0<br />

3 = 2.0m<br />

Short direction l 2<br />

3 = 5.4<br />

3 = 1.8m<br />

The thickness of the drop panel is 1.25h = 1.25 × 140 = 175 mm. Increase drop panel thickness<br />

to 220 mm to provide adequate thickness for punching shear and to avoid the use of a high<br />

percentage of steel reinforcement. All dimensions are shown in Fig. 17.41.<br />

2. Calculate factored loads:<br />

q u = 1.2 × 8.6 + 1.6 × 11 = 28 kN∕m 2

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!