24.02.2017 Views

Structural Concrete - Hassoun

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

17.10 Transfer of Unbalanced Moments to Columns 665<br />

3. For transfer by shear at exterior column, the critical section is located at a distance d/2 from the<br />

face of the column (Fig. 17.28).<br />

q u = 330 psf<br />

(<br />

V u = 0.33 20 × 12.83 − 23.95<br />

12 × 27.9 )<br />

= 83.1K<br />

12<br />

Locate the centroid of the critical section by taking moments about AB:<br />

(<br />

2 23.95 × 23.95 )<br />

=(2 × 23.95 + 27.9)x<br />

2<br />

l<br />

Therefore, x l = 7.6 in. The area of the critical section A c is 2(23.95 × 7.9) + (27.9 × 7.9) =<br />

599 in. 2 Calculate J c = I x + I y for the two equal areas (7.9 × 23.95) with sides parallel to the<br />

direction of moment and the area (7.9 × 27.9) perpendicular to the direction of moment, all about<br />

the axis through CD.<br />

J c = I y + I x = ∑ ( )<br />

bh 3<br />

12 + Ax2<br />

= 2<br />

[7.9 (23.95)3<br />

12<br />

( ) 23.95 2<br />

]<br />

+(7.9 × 23.95) − 7.6<br />

2<br />

[ 27.9<br />

+(1)<br />

12 (7.9)3] +[(27.9 × 7.9)(7.6) 2 ]=39,208 in. 4<br />

or by using Eq. 17.31 for an exterior column. Calculate the maximum and minimum nominal<br />

shear stresses using Eq. 17.27:<br />

v max = V u<br />

+ M v c = 83,100<br />

A c J c 599 + 40.2(12,000)(7.6) = 232 psi<br />

39,208<br />

v min = 138 psi<br />

Allowable v c = φ4 √ √<br />

f c ′ = 0.75 × 4 4000 = 190 psi<br />

Shear stress is greater than the allowable v c , so increase the slab thickness f c ′ or use shear reinforcement.<br />

4. Check the concentration of reinforcement at the exterior column; that is, check that the flexural<br />

capacity of the section is adequate to transfer the negative moment into the exterior column.<br />

The critical area of the slab extends 1.5h on either side of the column, giving an area<br />

(20 + 3 × 9) = 47 in. wide and 9 in. deep. The total moment in the 120-in.-wide column strip is<br />

107 K ⋅ ft, as calculated ) in Example 17.4 (step 5). The moment in a width, c 2 + 3h = 47 in., is<br />

equal to 107 = 41.9K⋅ ft.<br />

(<br />

47<br />

120<br />

If equal spacing in the column strip is used, then the additional reinforcement within the 47-in.<br />

width will be needed for a moment equal to M f − 41.9 = 66 − 41.9 = 24.1 K ⋅ ft. The required<br />

A s = 0.73 in. 2 and four no. 4 bars (A s = 0.8 in. 2 ) may be used. An alternative solution is to arrange<br />

the reinforcement within the column strip to increase the reinforcement within a width of 47 in.<br />

The amount of steel needed within this width should be enough to resist a moment of 0.6 times<br />

the negative moment in the column strip, or 0.6 × 107 = 64.2 K ⋅ ft.<br />

Assume a = 1.0 in. Then<br />

A s =<br />

A s =<br />

M u<br />

φf y (d − a∕2)<br />

64.2(12)<br />

= 1.93 in.2<br />

0.9 × 60(7.9 − 0.5)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!